EA-535AC10-C01 C
14.56 kW
Defrost: None
Product code: EA-335AG6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,693 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 65.7 m² |
| Inner volume | 19.2 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 97 kg |
| Quantity | 3 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 495 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-335AG6-C01 C | None |
|---|---|
| EA-335AG6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.73 | 5.81 | 5.89 | 5.98 | 6.01 | 5.99 | 5.93 | 6.14 | 6.55 | 7.12 | 6.99 | 6.95 | 6.89 | 6.83 |
| 5 | 7.28 | 7.49 | 7.68 | 7.85 | 7.93 | 7.93 | 7.86 | 8.03 | 8.54 | 9.28 | 9.01 | 8.92 | 8.79 | 8.59 |
| 6 | 8.81 | 9.16 | 9.48 | 9.72 | 9.88 | 9.93 | 9.87 | 10.02 | 10.63 | 11.53 | 11.15 | 11.01 | 10.79 | 10.42 |
| 7 | 10.18 | 10.71 | 11.19 | 11.61 | 11.85 | 11.96 | 11.90 | 12.06 | 12.78 | 13.85 | 13.40 | 13.21 | 12.92 | 12.41 |
| 8 | 11.41 | 12.10 | 12.74 | 13.29 | 13.60 | 13.80 | 13.85 | 14.05 | 14.90 | 16.16 | 15.66 | 15.43 | 15.07 | 14.43 |
| 9 | 12.51 | 13.40 | 14.11 | 14.84 | 15.32 | 15.60 | 15.70 | 15.92 | 16.89 | 18.30 | 17.80 | 17.56 | 17.17 | 16.47 |
| 10 | 13.51 | 14.61 | 15.51 | 16.40 | 17.00 | 17.38 | 17.54 | 17.80 | 18.89 | 20.45 | 19.91 | 19.64 | 19.20 | 18.39 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 19.911 |
| SC2 | 0 | 8 | 14.046 |
| SC3 | -18 | 7 | 11.722 |
| SC4 | -25 | 6 | 9.477 |
| SC5 | -34 | 6 | 8.898 |
| A | 1857 mm |
|---|---|
| B | 673 mm |
| C | 525 mm |
| F | 495 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1857 mm |
|---|---|
| Width | 623 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.