EA-291AG7-C04 C
104.65 kW
Defrost: None
Product code: EA-563FD4-C08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 73,309 m³/h |
|---|---|
| Air throw | 43 m |
| External surface | 522.1 m² |
| Inner volume | 107.2 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 635 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 9,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 75.0 dB(A) |
|---|---|
| Sound power | 99.0 dB(A) |
| Energy class | E |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø66,7 |
| EA-563FD4-C08 C | None |
|---|---|
| EA-563FD4-C08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 39.58 | 40.32 | 40.96 | 41.52 | 41.64 | 41.60 | 41.38 | 42.11 | 44.61 | 48.26 | 47.18 | 46.78 | 46.20 | 45.34 |
| 5 | 50.81 | 52.80 | 54.16 | 55.55 | 56.27 | 56.48 | 56.30 | 57.13 | 60.68 | 65.70 | 64.13 | 63.58 | 62.80 | 61.62 |
| 6 | 60.39 | 63.51 | 66.34 | 68.83 | 70.47 | 71.47 | 71.95 | 73.15 | 77.83 | 84.39 | 82.30 | 81.52 | 80.37 | 78.59 |
| 7 | 68.76 | 73.22 | 77.27 | 80.80 | 83.23 | 84.75 | 85.56 | 86.93 | 92.47 | 100.52 | 98.49 | 97.69 | 96.49 | 94.55 |
| 8 | 76.36 | 82.28 | 87.71 | 92.46 | 95.84 | 98.04 | 99.28 | 100.91 | 107.35 | 116.74 | 114.37 | 113.40 | 111.93 | 109.48 |
| 9 | ≈ 83.22 | 90.66 | 97.58 | 103.71 | 108.18 | 111.22 | 113.02 | 114.99 | 122.36 | 133.18 | 130.52 | 129.39 | 127.66 | 124.72 |
| 10 | ≈ 89.34 | 98.36 | 106.88 | 114.49 | 120.21 | 124.19 | 126.69 | 129.09 | 137.44 | 149.68 | 146.86 | 145.59 | 143.62 | 140.21 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 35.16 | 35.49 | 35.77 | 36.17 | 36.31 | 36.28 | 36.12 | 36.88 | 39.24 | 42.52 | 41.67 | 41.35 | 40.90 | 40.23 |
| 5 | 45.25 | 46.43 | 47.47 | 48.36 | 48.76 | 48.79 | 48.55 | 49.16 | 52.26 | 56.65 | 55.37 | 54.93 | 54.30 | 53.38 |
| 6 | 54.75 | 56.73 | 58.76 | 60.47 | 61.44 | 61.82 | 61.72 | 62.47 | 66.31 | 71.83 | 69.98 | 69.29 | 68.30 | 66.75 |
| 7 | 62.61 | 65.86 | 68.84 | 71.45 | 73.19 | 74.24 | 74.72 | 75.79 | 80.57 | 87.54 | 85.58 | 84.69 | 83.35 | 81.21 |
| 8 | 69.86 | 74.31 | 78.35 | 81.89 | 84.32 | 85.83 | 86.60 | 87.81 | 93.33 | 101.43 | 99.21 | 98.30 | 96.94 | 94.67 |
| 9 | 76.48 | 82.21 | 87.45 | 92.05 | 95.30 | 97.39 | 98.54 | 99.96 | 106.25 | 115.49 | 112.98 | 111.91 | 110.29 | 107.55 |
| 10 | ≈ 82.47 | 89.54 | 96.10 | 101.88 | 106.05 | 108.80 | 110.40 | 112.16 | 119.26 | 129.65 | 126.94 | 125.71 | 123.85 | 120.65 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 146.860 | 126.935 |
| SC2 | 0 | 8 | 100.908 | 87.812 |
| SC3 | -18 | 7 | 81.896 | 72.241 |
| SC4 | -25 | 6 | 66.339 | 58.757 |
| SC5 | -34 | 6 | 61.138 | 55.328 |
| A | 5415 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| G | 985 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 1 x Ø54 |
| D OUT | 1 x Ø66,7 |
| Length | 5415 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.