EA-163ED10-C01 C
9.63 kW
Defrost: None
Product code: EA-630BC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,787 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 25.6 m² |
| Inner volume | 11.7 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 77 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 372 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 50.0 dB(A) |
|---|---|
| Sound power | 72.0 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-630BC10-C01 C | None |
|---|---|
| EA-630BC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.49 | 3.50 | 3.52 | 3.54 | 3.53 | 3.51 | 3.47 | 3.53 | 3.74 | 4.03 | 3.93 | 3.88 | 3.83 | 3.74 |
| 5 | 4.58 | 4.67 | 4.76 | 4.84 | 4.87 | 4.87 | 4.83 | 4.90 | 5.20 | 5.63 | 5.48 | 5.43 | 5.36 | 5.26 |
| 6 | 5.65 | 5.84 | 6.02 | 6.16 | 6.26 | 6.30 | 6.29 | 6.36 | 6.75 | 7.32 | 7.12 | 7.04 | 6.93 | 6.76 |
| 7 | 6.62 | 6.93 | 7.21 | 7.47 | 7.66 | 7.75 | 7.78 | 7.88 | 8.36 | 9.06 | 8.84 | 8.75 | 8.61 | 8.39 |
| 8 | 7.45 | 7.87 | 8.26 | 8.62 | 8.83 | 9.00 | 9.11 | 9.26 | 9.85 | 10.73 | 10.52 | 10.43 | 10.30 | 10.08 |
| 9 | 8.22 | 8.76 | 9.22 | 9.67 | 10.01 | 10.25 | 10.40 | 10.58 | 11.26 | 12.26 | 12.04 | 11.94 | 11.79 | 11.53 |
| 10 | 8.92 | 9.54 | 10.17 | 10.74 | 11.16 | 11.47 | 11.68 | 11.90 | 12.67 | 13.80 | 13.57 | 13.46 | 13.30 | 13.00 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.572 |
| SC2 | 0 | 8 | 9.258 |
| SC3 | -18 | 7 | 7.553 |
| SC4 | -25 | 6 | 6.017 |
| SC5 | -34 | 6 | 5.697 |
| A | 2557 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 385 mm |
| E2 | 367 mm |
| E | 2235 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2557 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.