EA-163GC10-C08 C
14.53 kW
Defrost: None
Product code: EA-630BE6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,404 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 59.9 m² |
| Inner volume | 16.5 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 90 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 372 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 52.0 dB(A) |
|---|---|
| Sound power | 74.1 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-630BE6-C01 C | None |
|---|---|
| EA-630BE6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.56 | 5.65 | 5.75 | 5.83 | 5.86 | 5.85 | 5.79 | 5.97 | 6.37 | 6.91 | 6.78 | 6.74 | 6.68 | 6.61 |
| 5 | 7.10 | 7.33 | 7.55 | 7.73 | 7.82 | 7.83 | 7.77 | 7.95 | 8.45 | 9.17 | 8.92 | 8.83 | 8.71 | 8.52 |
| 6 | 8.60 | 8.99 | 9.35 | 9.66 | 9.83 | 9.88 | 9.84 | 10.00 | 10.62 | 11.52 | 11.16 | 11.02 | 10.81 | 10.48 |
| 7 | 9.90 | 10.45 | 10.96 | 11.41 | 11.71 | 11.82 | 11.86 | 12.07 | 12.82 | 13.92 | 13.49 | 13.31 | 13.03 | 12.57 |
| 8 | 11.05 | 11.79 | 12.39 | 12.99 | 13.40 | 13.63 | 13.71 | 13.94 | 14.81 | 16.08 | 15.66 | 15.46 | 15.17 | 14.66 |
| 9 | 12.09 | 12.95 | 13.81 | 14.57 | 15.09 | 15.43 | 15.57 | 15.83 | 16.81 | 18.24 | 17.78 | 17.55 | 17.21 | 16.60 |
| 10 | ≈ 13.04 | 14.09 | 15.15 | 16.09 | 16.76 | 17.20 | 17.41 | 17.72 | 18.82 | 20.42 | 19.92 | 19.67 | 19.27 | 18.57 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 19.921 |
| SC2 | 0 | 8 | 13.943 |
| SC3 | -18 | 7 | 11.547 |
| SC4 | -25 | 6 | 9.352 |
| SC5 | -34 | 6 | 8.693 |
| A | 2557 mm |
|---|---|
| B | 573 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 385 mm |
| E2 | 367 mm |
| E | 2235 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 2557 mm |
|---|---|
| Width | 573 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.