EA-163EG7-C01 C
14.53 kW
Defrost: None
Product code: EA-250AC10-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 14,484 m³/h |
|---|---|
| Air throw | 21 m |
| External surface | 31.7 m² |
| Inner volume | 14.9 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 95 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 1,420 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 81.8 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-250AC10-C09 C | None |
|---|---|
| EA-250AC10-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.10 | 5.02 | 4.96 | 4.91 | 4.84 | 4.76 | 4.68 | 4.67 | 4.92 | 5.29 | 5.12 | 5.05 | 4.97 | 4.84 |
| 5 | 6.94 | 6.94 | 6.95 | 6.97 | 6.93 | 6.85 | 6.75 | 6.75 | 7.14 | 7.68 | 7.43 | 7.33 | 7.20 | 6.99 |
| 6 | 8.77 | 8.90 | 9.01 | 9.13 | 9.17 | 9.14 | 9.06 | 9.07 | 9.60 | 10.34 | 10.00 | 9.88 | 9.70 | 9.44 |
| 7 | 10.46 | 10.78 | 11.08 | 11.34 | 11.48 | 11.53 | 11.48 | 11.53 | 12.21 | 13.18 | 12.79 | 12.63 | 12.41 | 12.05 |
| 8 | 11.92 | 12.39 | 12.84 | 13.25 | 13.54 | 13.69 | 13.80 | 13.96 | 14.83 | 16.11 | 15.70 | 15.53 | 15.27 | 14.86 |
| 9 | 13.25 | 13.91 | 14.45 | 15.01 | 15.41 | 15.68 | 15.85 | 16.05 | 17.06 | 18.55 | 18.19 | 18.04 | 17.82 | 17.44 |
| 10 | 14.49 | 15.28 | 16.06 | 16.78 | 17.31 | 17.68 | 17.92 | 18.17 | 19.32 | 21.02 | 20.63 | 20.47 | 20.22 | 19.79 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 20.634 |
| SC2 | 0 | 8 | 13.955 |
| SC3 | -18 | 7 | 11.407 |
| SC4 | -25 | 6 | 9.009 |
| SC5 | -34 | 6 | 8.806 |
| A | 2087 mm |
|---|---|
| B | 590 mm |
| C | 685 mm |
| F | 395 mm |
| E1 | 868 mm |
| E | 1735 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2087 mm |
|---|---|
| Width | 590 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.