EB-140AE4-B01 C
6.85 kW
Defrost: None
Product code: EB-330AE7-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,053 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 23.4 m² |
| Inner volume | 6.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 44 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-330AE7-B05 C | None |
|---|---|
| EB-330AE7-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.72 | 2.72 | 2.73 | 2.74 | 2.74 | 2.73 | 2.70 | 2.78 | 2.97 | 3.22 | 3.16 | 3.14 | 3.12 | 3.09 |
| 5 | 3.53 | 3.56 | 3.60 | 3.64 | 3.66 | 3.64 | 3.61 | 3.67 | 3.91 | 4.24 | 4.12 | 4.08 | 4.02 | 3.93 |
| 6 | 4.32 | 4.40 | 4.48 | 4.56 | 4.60 | 4.60 | 4.56 | 4.62 | 4.90 | 5.31 | 5.14 | 5.07 | 4.97 | 4.82 |
| 7 | 5.08 | 5.22 | 5.36 | 5.49 | 5.56 | 5.58 | 5.54 | 5.60 | 5.93 | 6.42 | 6.21 | 6.13 | 6.00 | 5.78 |
| 8 | 5.77 | 5.97 | 6.18 | 6.36 | 6.48 | 6.54 | 6.53 | 6.60 | 6.99 | 7.56 | 7.32 | 7.22 | 7.06 | 6.80 |
| 9 | 6.40 | 6.68 | 6.95 | 7.19 | 7.34 | 7.43 | 7.44 | 7.53 | 7.99 | 8.65 | 8.42 | 8.31 | 8.14 | 7.83 |
| 10 | 7.05 | 7.40 | 7.73 | 8.00 | 8.20 | 8.32 | 8.35 | 8.45 | 8.96 | 9.70 | 9.45 | 9.32 | 9.13 | 8.82 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 9.448 |
| SC2 | 0 | 8 | 6.596 |
| SC3 | -18 | 7 | 5.520 |
| SC4 | -25 | 6 | 4.483 |
| SC5 | -34 | 6 | 4.343 |
| A | 1617 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1295 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1617 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.