EB-430AE4-B05 C
9.56 kW
Defrost: None
Product code: EB-430AE6-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,963 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 35.8 m² |
| Inner volume | 8.6 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 55 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-430AE6-B05 C | None |
|---|---|
| EB-430AE6-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.88 | 3.89 | 3.91 | 3.94 | 3.95 | 3.93 | 3.90 | 4.02 | 4.29 | 4.66 | 4.57 | 4.55 | 4.51 | 4.47 |
| 5 | 5.01 | 5.06 | 5.13 | 5.20 | 5.22 | 5.21 | 5.16 | 5.26 | 5.59 | 6.07 | 5.90 | 5.84 | 5.75 | 5.62 |
| 6 | 6.09 | 6.22 | 6.35 | 6.47 | 6.53 | 6.54 | 6.49 | 6.57 | 6.97 | 7.56 | 7.32 | 7.22 | 7.08 | 6.86 |
| 7 | 7.12 | 7.34 | 7.55 | 7.75 | 7.85 | 7.89 | 7.85 | 7.93 | 8.40 | 9.10 | 8.81 | 8.68 | 8.50 | 8.21 |
| 8 | 8.05 | 8.36 | 8.66 | 8.93 | 9.10 | 9.17 | 9.18 | 9.29 | 9.85 | 10.66 | 10.33 | 10.18 | 9.97 | 9.61 |
| 9 | 8.99 | 9.39 | 9.72 | 10.07 | 10.29 | 10.41 | 10.43 | 10.55 | 11.19 | 12.11 | 11.78 | 11.63 | 11.41 | 11.02 |
| 10 | 9.81 | 10.33 | 10.80 | 11.23 | 11.48 | 11.64 | 11.69 | 11.83 | 12.54 | 13.57 | 13.20 | 13.03 | 12.78 | 12.33 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.201 |
| SC2 | 0 | 8 | 9.291 |
| SC3 | -18 | 7 | 7.798 |
| SC4 | -25 | 6 | 6.349 |
| SC5 | -34 | 6 | 6.124 |
| A | 2037 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1715 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2037 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.