EB-430AE7-B01 C
10.25 kW
Defrost: None
Product code: EB-430BE7-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,515 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 37.2 m² |
| Inner volume | 10.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 64 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-430BE7-B05 C | None |
|---|---|
| EB-430BE7-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.02 | 4.05 | 4.09 | 4.13 | 4.15 | 4.15 | 4.12 | 4.22 | 4.49 | 4.88 | 4.78 | 4.75 | 4.71 | 4.65 |
| 5 | 5.17 | 5.26 | 5.36 | 5.45 | 5.50 | 5.51 | 5.49 | 5.57 | 5.92 | 6.43 | 6.25 | 6.19 | 6.10 | 5.96 |
| 6 | 6.26 | 6.44 | 6.62 | 6.78 | 6.88 | 6.92 | 6.91 | 6.99 | 7.42 | 8.05 | 7.82 | 7.72 | 7.58 | 7.35 |
| 7 | 7.28 | 7.56 | 7.84 | 8.09 | 8.26 | 8.34 | 8.35 | 8.44 | 8.96 | 9.71 | 9.43 | 9.31 | 9.13 | 8.82 |
| 8 | 8.20 | 8.58 | 8.95 | 9.29 | 9.51 | 9.65 | 9.71 | 9.84 | 10.45 | 11.34 | 11.06 | 10.93 | 10.71 | 10.32 |
| 9 | 9.12 | 9.61 | 10.08 | 10.46 | 10.75 | 10.94 | 11.03 | 11.18 | 11.87 | 12.87 | 12.56 | 12.41 | 12.18 | 11.77 |
| 10 | 9.93 | 10.55 | 11.13 | 11.64 | 12.01 | 12.22 | 12.35 | 12.53 | 13.30 | 14.42 | 14.08 | 13.91 | 13.64 | 13.17 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 14.079 |
| SC2 | 0 | 8 | 9.841 |
| SC3 | -18 | 7 | 8.167 |
| SC4 | -25 | 6 | 6.617 |
| SC5 | -34 | 6 | 6.302 |
| A | 2357 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2357 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |