ED-130AE7-C21 C
2.61 kW
Defrost: None
Product code: ED-130AC4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,331 m³/h |
|---|---|
| Air throw | 4 m |
| External surface | 9.8 m² |
| Inner volume | 1.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 33 kg |
| Quantity | 1 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 62 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 64.1 dB(A) |
| Energy class | B |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø12,7 |
| ED-130AC4-C21 C | None |
|---|---|
| ED-130AC4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.91 | 0.95 | 0.99 | 1.02 | 1.04 | 1.05 | 1.05 | 1.08 | 1.15 | 1.25 | 1.23 | 1.22 | 1.21 | 1.20 |
| 5 | 1.13 | 1.21 | 1.28 | 1.34 | 1.38 | 1.41 | 1.42 | 1.45 | 1.54 | 1.68 | 1.64 | 1.63 | 1.61 | 1.58 |
| 6 | 1.33 | 1.43 | 1.53 | 1.61 | 1.68 | 1.72 | 1.74 | 1.78 | 1.90 | 2.07 | 2.03 | 2.02 | 1.99 | 1.96 |
| 7 | ≈ 1.52 | 1.66 | 1.78 | 1.89 | 1.97 | 2.03 | 2.06 | 2.11 | 2.25 | 2.45 | 2.41 | 2.39 | 2.36 | 2.31 |
| 8 | ≈ 1.68 | 1.85 | 2.01 | 2.15 | 2.26 | 2.34 | 2.39 | 2.43 | 2.59 | 2.82 | 2.78 | 2.76 | 2.72 | 2.66 |
| 9 | ≈ 1.82 | 2.02 | 2.22 | 2.40 | 2.52 | 2.62 | 2.69 | 2.76 | 2.94 | 3.21 | 3.16 | 3.14 | 3.10 | 3.03 |
| 10 | ≈ 1.49 | ≈ 2.18 | 2.42 | 2.61 | 2.78 | 2.91 | 3.00 | 3.08 | 3.29 | 3.59 | 3.54 | 3.52 | 3.48 | 3.40 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.543 |
| SC2 | 0 | 8 | 2.430 |
| SC3 | -18 | 7 | 1.927 |
| SC4 | -25 | 6 | 1.528 |
| SC5 | -34 | 6 | 1.353 |
| A | 848 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 535 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø12,7 |
| Length | 848 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.