ED-130AE4-C25 C
2.81 kW
Defrost: None
Product code: ED-130AE4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,188 m³/h |
|---|---|
| Air throw | 4 m |
| External surface | 19.0 m² |
| Inner volume | 4.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 38 kg |
| Quantity | 1 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 62 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 44.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | B |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| ED-130AE4-C21 C | None |
|---|---|
| ED-130AE4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.26 | 1.27 | 1.28 | 1.30 | 1.31 | 1.31 | 1.31 | 1.34 | 1.43 | 1.55 | 1.53 | 1.52 | 1.51 | 1.49 |
| 5 | 1.60 | 1.63 | 1.67 | 1.70 | 1.71 | 1.72 | 1.71 | 1.74 | 1.85 | 2.01 | 1.96 | 1.94 | 1.92 | 1.88 |
| 6 | 1.92 | 1.99 | 2.05 | 2.10 | 2.13 | 2.14 | 2.14 | 2.16 | 2.29 | 2.49 | 2.42 | 2.39 | 2.35 | 2.28 |
| 7 | 2.25 | 2.34 | 2.43 | 2.51 | 2.55 | 2.57 | 2.57 | 2.60 | 2.75 | 2.98 | 2.89 | 2.86 | 2.80 | 2.71 |
| 8 | 2.53 | 2.67 | 2.80 | 2.90 | 2.97 | 3.01 | 3.01 | 3.04 | 3.22 | 3.49 | 3.39 | 3.34 | 3.28 | 3.16 |
| 9 | 2.79 | 2.97 | 3.13 | 3.27 | 3.36 | 3.41 | 3.43 | 3.48 | 3.69 | 4.00 | 3.88 | 3.83 | 3.75 | 3.61 |
| 10 | 3.02 | 3.24 | 3.44 | 3.60 | 3.72 | 3.80 | 3.84 | 3.88 | 4.12 | 4.47 | 4.36 | 4.31 | 4.22 | 4.08 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 4.359 |
| SC2 | 0 | 8 | 3.039 |
| SC3 | -18 | 7 | 2.523 |
| SC4 | -25 | 6 | 2.046 |
| SC5 | -34 | 6 | 1.939 |
| A | 848 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 535 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 848 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.