ED-230AE7-C21 C
5.43 kW
Defrost: None
Product code: ED-135AE4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,190 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 27.4 m² |
| Inner volume | 6.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 46 kg |
| Quantity | 1 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 165 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | C |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø28 |
| ED-135AE4-C21 C | None |
|---|---|
| ED-135AE4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.20 | 2.18 | 2.18 | 2.19 | 2.19 | 2.18 | 2.17 | 2.23 | 2.38 | 2.59 | 2.55 | 2.54 | 2.52 | 2.50 |
| 5 | 2.87 | 2.87 | 2.88 | 2.89 | 2.89 | 2.88 | 2.86 | 2.91 | 3.09 | 3.36 | 3.28 | 3.25 | 3.21 | 3.16 |
| 6 | 3.54 | 3.56 | 3.60 | 3.63 | 3.64 | 3.63 | 3.59 | 3.63 | 3.86 | 4.18 | 4.05 | 4.01 | 3.95 | 3.85 |
| 7 | 4.20 | 4.25 | 4.32 | 4.39 | 4.42 | 4.41 | 4.37 | 4.40 | 4.66 | 5.04 | 4.88 | 4.81 | 4.72 | 4.57 |
| 8 | 4.83 | 4.95 | 5.06 | 5.16 | 5.21 | 5.21 | 5.17 | 5.20 | 5.50 | 5.94 | 5.74 | 5.66 | 5.54 | 5.34 |
| 9 | 5.41 | 5.59 | 5.77 | 5.92 | 6.00 | 6.02 | 5.99 | 6.02 | 6.36 | 6.87 | 6.64 | 6.54 | 6.40 | 6.15 |
| 10 | 5.93 | 6.18 | 6.40 | 6.61 | 6.73 | 6.79 | 6.78 | 6.84 | 7.23 | 7.80 | 7.56 | 7.44 | 7.27 | 6.98 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.555 |
| SC2 | 0 | 8 | 5.197 |
| SC3 | -18 | 7 | 4.406 |
| SC4 | -25 | 6 | 3.595 |
| SC5 | -34 | 6 | 3.545 |
| A | 948 mm |
|---|---|
| B | 1030 mm |
| C | 285 mm |
| F | 985 mm |
| G | 367 mm |
| E1 | 635 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø28 |
| Length | 948 mm |
|---|---|
| Width | 1030 mm |
| Height | 367 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.