EG-230BE7-C25 C
4.21 kW
Defrost: None
Product code: EG-325BE7-C23 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,818 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 16.7 m² |
| Inner volume | 4.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 37 kg |
| Quantity | 3 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 195 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 42.0 dB(A) |
|---|---|
| Sound power | 63.4 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EG-325BE7-C23 C | None |
|---|---|
| EG-325BE7-C23 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.65 | 1.67 | 1.70 | 1.72 | 1.74 | 1.73 | 1.72 | 1.78 | 1.90 | 2.07 | 2.03 | 2.01 | 2.00 | 1.98 |
| 5 | 2.10 | 2.16 | 2.21 | 2.26 | 2.29 | 2.29 | 2.28 | 2.32 | 2.47 | 2.69 | 2.61 | 2.58 | 2.54 | 2.48 |
| 6 | 2.53 | 2.63 | 2.72 | 2.80 | 2.85 | 2.86 | 2.85 | 2.90 | 3.07 | 3.34 | 3.24 | 3.20 | 3.14 | 3.05 |
| 7 | 2.94 | 3.08 | 3.21 | 3.33 | 3.40 | 3.44 | 3.44 | 3.48 | 3.70 | 4.01 | 3.89 | 3.85 | 3.78 | 3.66 |
| 8 | 3.30 | 3.48 | 3.66 | 3.81 | 3.91 | 3.97 | 3.99 | 4.05 | 4.30 | 4.67 | 4.56 | 4.51 | 4.43 | 4.29 |
| 9 | 3.63 | 3.87 | 4.09 | 4.29 | 4.42 | 4.50 | 4.53 | 4.60 | 4.88 | 5.30 | 5.18 | 5.12 | 5.04 | 4.89 |
| 10 | 3.97 | 4.26 | 4.53 | 4.76 | 4.93 | 5.02 | 5.07 | 5.15 | 5.47 | 5.93 | 5.80 | 5.74 | 5.64 | 5.47 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.800 |
| SC2 | 0 | 8 | 4.054 |
| SC3 | -18 | 7 | 3.364 |
| SC4 | -25 | 6 | 2.719 |
| SC5 | -34 | 6 | 2.557 |
| A | 1426 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 378 mm |
| E2 | 360 mm |
| E | 1115 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 1426 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.