Skip to Content

Blast freezer EK-K-s-263BE10-B08 C ED

Defrost: Electric

Blast freezer EK-K-s-263BE10-B08 C
Illustrative photo

Producer: Karyer · Line: EK-K (Blast Freezers)

Product code: EK-K-s-263BE10-B08 C ED

Cooling capacity i
33.49 kW
Air flow
29,740 m³/h
Fin spacing
10.0 mm
Fans
2 × ⌀630 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EK-K — EK-K - blast freezer
  • B
    Fan direction: s — Sucking (suction) fan
  • C
    Number of fans: 2 — Number of fans (one digit).
  • D
    Fan diameter: 63 — Ø630 mm
  • E
    Dimensional data - coil size letter: B — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • F
    Dimensional data - tube rows: E — 6 tube rows
  • G
    Fin spacing: 10 — Fin spacing about 10 mm
  • H
    Generation code: B — Generation B
  • I
    Fan data: 08 — Ø630: 400V/3Ph/50Hz, 4-pole

Data

Evaporator
Air flow 29,740 m³/h
External surface 109.9 m²
Inner volume 46.0 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 318 kg
Fans
Quantity 2
Diameter 630 mm
Speed 1,340 rpm
Power 3,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 72.0 dB(A)
Sound power 95.0 dB(A)
Energy class E
Connections
Inlet Ø19
Outlet Ø42
Defrost
EK-K-s-263BE10-B08 C None
EK-K-s-263BE10-B08 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
31.868 kW
Low speed (Y)
27.292 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 13.05 12.62 12.35 12.21 12.06 11.92 11.78 11.85 12.54 13.54 13.22 13.10 12.94 12.71
5 16.02 15.59 15.31 16.82 16.59 16.34 16.09 16.17 17.11 18.44 17.92 17.74 17.47 17.09
6 20.48 20.11 19.87 21.91 21.64 21.32 20.96 20.98 22.18 23.88 23.13 22.87 22.51 21.96
7 25.03 24.79 24.67 27.30 27.07 26.72 26.29 26.25 27.73 29.83 28.81 28.45 27.93 27.16
8 29.43 29.45 29.52 32.90 32.76 32.43 31.95 31.87 33.65 36.20 34.90 34.42 33.73 32.66
9 37.41 37.80 38.19 38.54 38.50 38.26 37.82 37.72 39.84 42.87 41.32 40.72 39.86 38.48
10 41.88 42.59 43.37 44.04 44.30 44.21 43.84 43.76 46.22 49.80 48.04 47.34 46.31 44.66

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 11.52 11.15 10.95 10.85 10.75 10.65 10.56 10.71 11.34 12.27 12.01 11.92 11.79 11.60
5 14.00 13.61 13.38 14.73 14.57 14.39 14.21 14.34 15.22 16.45 16.05 15.91 15.71 15.40
6 17.81 17.43 17.21 18.98 18.78 18.54 18.26 18.34 19.42 20.95 20.34 20.13 19.84 19.41
7 21.73 21.38 21.22 23.49 23.29 23.01 22.67 22.68 23.98 25.83 24.99 24.69 24.26 23.62
8 25.58 25.41 25.36 28.19 28.01 27.73 27.34 27.29 28.83 31.05 29.97 29.57 29.00 28.11
9 32.59 32.64 32.78 32.95 32.88 32.63 32.21 32.13 33.93 36.55 35.24 34.74 34.01 32.86
10 36.62 36.97 37.36 37.74 37.81 37.63 37.24 37.10 39.18 42.20 40.72 40.12 39.25 37.84

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 48.04240.719
SC2 0 8 31.86827.292
SC3 -18 7 27.22623.423
SC4 -25 6 19.86917.209
SC5 -34 6 20.42217.747

Dimensions

Dimension drawing of EK-K-s-263BE10-B08 C
Dimension drawing
Dimensions as drawn
A 1460 mm
B 1050 mm
C 1935 mm
F 840 mm
G 1035 mm
E 2050 mm
D IN 2 x Ø19
D OUT 2 x Ø42
Overall [mm]
Length 1460 mm
Width 1050 mm
Height 2050 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.