Product code: BSCR-2P-ZB95

Refrigerating capacity i
42.30 kW
Absorbed power
21.00 kW
COP
2.01
Compressors
2 × scroll compressors
Receiver
60 l

Nominal conditions: evaporating -10 °C, condensing 45 °C (dew points), superheat 10 K, subcooling 3 K; refrigerant R404A where rated.

Model nomenclature

How to read the code of this model.

  • A
    Series: BSCR — Sphinx CompactRack
  • B
    Number of compressors: 2 — Number of identical compressors on the rack (2 to 4).
  • C
    Application: P — Medium / high temperature
  • D
    Compressor model: ZB95 — Model of the compressors fitted (all compressors of a rack are the same model); an 'EVI' tail marks enhanced vapour injection.

Data

Rack
ApplicationMedium temperature (MT)
Compressors2 × scroll compressors
Liquid receiver 60 l
Net weight 348 kg
Electrical
Max. current 46.0 A
Starting current 163.0 A
Connections
Suction 2"1/8
Liquid 1"1/8
Discharge 1"1/8
Liquid set
L / W / H 666/402/1366 mm
Weight 80 kg

Performance

Evaporating temperature -50…5 °C, condensing temperature 20…55 °C (dew points); superheat 10 K, subcooling 3 K.

R404A, evaporating -10 °C, condensing 45 °C (dew points; superheat 10 K, subcooling 3 K)

Refrigerating capacity
42.30 kW
Absorbed power
21.00 kW
COP
2.01
Current
38.4 A
Heat rejection
63.30 kW

Heat rejection = refrigerating capacity + absorbed power. COP = refrigerating capacity / absorbed power.

Standard points

Te [°C] Tc [°C] Refrigerating capacity [kW] Absorbed power [kW] COP Current [A]
-10 40 46.70 18.80 2.48 35.2
-10 45 42.30 21.00 2.01 38.4

Evaporating × condensing temperature (dew points)

R404A; rows: condensing temperature Tc [°C]; columns: evaporating temperature Te [°C]. The highlighted cell is the nominal point. "—": outside the compressors' operating envelope.

Capacity [kW]

Capacity [kW]: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -25-20-15-10-505
20 32.70 40.90 50.50 61.70 74.70 89.60 not rated
25 30.50 38.40 47.60 58.30 70.60 84.80 100.80
30 28.10 35.70 44.50 54.70 66.40 79.80 95.00
35 25.40 32.80 41.20 50.80 61.90 74.60 89.00
40 22.40 29.50 37.60 46.70 57.20 69.20 82.80
45 19.00 26.00 33.70 42.30 52.20 63.50 76.30
50 not rated 22.00 29.40 37.60 47.00 57.50 69.60
55 not rated not rated 24.80 32.60 41.40 51.30 62.60

Power [kW]

Power [kW]: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -25-20-15-10-505
20 11.60 11.90 12.10 12.50 12.80 13.00 not rated
25 13.00 13.20 13.40 13.70 14.00 14.30 14.60
30 14.70 14.80 14.90 15.20 15.50 15.80 16.10
35 16.60 16.60 16.70 16.80 17.10 17.40 17.70
40 18.90 18.70 18.70 18.80 18.90 19.20 19.40
45 21.50 21.20 21.00 21.00 21.10 21.30 21.50
50 not rated 24.00 23.70 23.60 23.60 23.60 23.80
55 not rated not rated 26.90 26.60 26.40 26.40 26.40

COP

COP: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -25-20-15-10-505
20 2.82 3.44 4.17 4.94 5.84 6.89 not rated
25 2.35 2.91 3.55 4.26 5.04 5.93 6.90
30 1.91 2.41 2.99 3.60 4.28 5.05 5.90
35 1.53 1.98 2.47 3.02 3.62 4.29 5.03
40 1.19 1.58 2.01 2.48 3.03 3.60 4.27
45 0.88 1.23 1.60 2.01 2.47 2.98 3.55
50 not rated 0.92 1.24 1.59 1.99 2.44 2.92
55 not rated not rated 0.92 1.23 1.57 1.94 2.37

Dimensions

Dimension drawing of BSCR-2P-ZB95
Dimension drawing
Dimensions as drawn
L 1310 mm
P 825 mm
H 1255 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.