Skip to Content

Unit cooler EA-DA-350BE7-C21 C ED

Defrost: Electric

Unit cooler EA-DA-350BE7-C21 C
Illustrative photo

Producer: Karyer · Line: EA-DA (Fruit and Vegetable)

Product code: EA-DA-350BE7-C21 C ED

Cooling capacity i
36.29 kW
Air flow
21,663 m³/h
Fin spacing
7.0 mm
Air throw
24 m
Fans
3 × ⌀500 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EA-DA — EA-DA - fruit and vegetable unit cooler (blowing fans)
  • C
    Number of fans: 3 — Number of fans (one digit).
  • D
    Fan diameter: 50 — Ø500 mm
  • E
    Dimensional data - coil size letter: B — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • F
    Dimensional data - tube rows: E — 6 tube rows
  • G
    Fin spacing: 7 — Fin spacing about 7 mm
  • H
    Generation code: C — Generation C
  • I
    Fan data: 21 — Ø350: 230V/1Ph/50Hz, 4-pole; Ø500: 230V/1Ph/50Hz, 4-pole

Data

Evaporator
Air flow 21,663 m³/h
Air throw 24 m
External surface 176.8 m²
Inner volume 50.0 dm³
Fin spacing 7.0 mm
Fin materialAluminium
Net weight 250 kg
Fans
Quantity 3
Diameter 500 mm
Speed 1,300 rpm
Power 2,040 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 61.0 dB(A)
Sound power 83.9 dB(A)
Energy class D
Connections
Inlet Ø28
Outlet Ø42
Defrost
EA-DA-350BE7-C21 C None
EA-DA-350BE7-C21 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
34.974 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 13.84 14.10 14.29 14.53 14.63 14.64 14.59 14.79 15.72 17.03 16.66 16.52 16.31 15.99
5 17.57 18.21 18.78 19.27 19.54 19.64 19.58 19.77 21.00 22.75 22.21 22.01 21.72 21.29
6 21.02 21.98 22.96 23.81 24.36 24.66 24.76 25.03 26.58 28.82 28.12 27.84 27.44 26.78
7 23.91 25.41 26.79 28.02 28.89 29.46 29.80 30.23 32.15 34.97 34.26 33.93 33.43 32.60
8 ≈ 26.53 28.50 30.33 31.96 33.14 33.94 34.44 34.97 37.21 40.49 39.71 39.38 38.87 38.01
9 ≈ 28.89 31.37 33.69 35.76 37.29 38.36 39.05 39.72 42.28 46.02 45.19 44.81 44.24 43.23
10 ≈ 31.01 34.02 36.85 39.40 41.32 42.71 43.63 44.46 47.34 51.57 50.70 50.29 49.65 48.48

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 50.698
SC2 0 8 34.974
SC3 -18 7 28.404
SC4 -25 6 22.959
SC5 -34 6 21.282

Dimensions

Dimension drawing of EA-DA-350BE7-C21 C
Dimension drawing
Dimensions as drawn
A 3487 mm
B 950 mm
C 810 mm
F 710 mm
E1 1018 mm
E2 1000 mm
E 3035 mm
D IN 1 x Ø28
D OUT 1 x Ø42
Overall [mm]
Length 3487 mm
Width 950 mm
Height 810 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.