EA-DV-280GC10-A01 C
41.87 kW
Defrost: None
Product code: EA-DV-163GI4-A13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 15,882 m³/h |
|---|---|
| External surface | 271.2 m² |
| Inner volume | 54.0 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 345 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 87.3 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-DV-163GI4-A13 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 17.61 | 17.81 | 18.05 | 18.30 | 18.43 | 18.45 | 18.39 | 18.75 | 19.96 | 21.68 | 21.27 | 21.12 | 20.92 | 20.63 |
| 5 | 22.32 | 22.83 | 23.31 | 23.77 | 24.00 | 24.04 | 23.96 | 24.28 | 25.79 | 27.98 | 27.30 | 27.05 | 26.69 | 26.13 |
| 6 | 26.69 | 27.63 | 28.49 | 29.24 | 29.57 | 29.76 | 29.72 | 30.01 | 31.84 | 34.50 | 33.57 | 33.20 | 32.65 | 31.76 |
| 7 | 30.74 | 32.02 | 33.33 | 34.47 | 35.19 | 35.55 | 35.60 | 35.91 | 38.08 | 41.26 | 40.12 | 39.65 | 38.93 | 37.74 |
| 8 | 34.17 | 36.07 | 37.83 | 39.39 | 40.44 | 41.08 | 41.33 | 41.79 | 44.35 | 48.10 | 46.80 | 46.23 | 45.36 | 43.88 |
| 9 | 37.38 | 39.85 | 42.12 | 44.12 | 45.50 | 46.34 | 46.75 | 47.28 | 50.18 | 54.42 | 53.12 | 52.52 | 51.60 | 50.01 |
| 10 | ≈ 40.32 | 43.37 | 46.20 | 48.70 | 50.47 | 51.58 | 52.16 | 52.79 | 56.04 | 60.76 | 59.34 | 58.67 | 57.62 | 55.78 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 14.29 | 14.32 | 14.44 | 14.60 | 14.68 | 14.71 | 14.68 | 14.96 | 15.95 | 17.35 | 17.02 | 16.91 | 16.76 | 16.55 |
| 5 | 18.11 | 18.22 | 18.47 | 18.74 | 18.88 | 18.92 | 18.88 | 19.10 | 20.28 | 22.02 | 21.50 | 21.31 | 21.03 | 20.58 |
| 6 | 21.74 | 22.14 | 22.57 | 22.98 | 23.17 | 23.26 | 23.21 | 23.41 | 24.83 | 26.92 | 26.22 | 25.94 | 25.52 | 24.83 |
| 7 | 25.19 | 25.90 | 26.58 | 27.19 | 27.54 | 27.69 | 27.66 | 27.80 | 29.47 | 31.91 | 31.05 | 30.69 | 30.14 | 29.23 |
| 8 | 28.43 | 29.50 | 30.50 | 31.25 | 31.78 | 32.05 | 32.08 | 32.29 | 34.21 | 37.02 | 36.01 | 35.57 | 34.90 | 33.73 |
| 9 | 31.44 | 32.78 | 34.12 | 35.30 | 36.04 | 36.43 | 36.56 | 36.80 | 39.00 | 42.19 | 41.05 | 40.54 | 39.76 | 38.32 |
| 10 | 34.04 | 35.88 | 37.58 | 39.09 | 40.08 | 40.67 | 40.96 | 41.32 | 43.81 | 47.39 | 46.14 | 45.56 | 44.67 | 42.99 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 59.342 | 46.135 |
| SC2 | 0 | 8 | 41.786 | 32.285 |
| SC3 | -18 | 7 | 34.802 | 27.360 |
| SC4 | -25 | 6 | 28.494 | 22.567 |
| SC5 | -34 | 6 | 26.929 | 21.852 |
| A | 1725 mm |
|---|---|
| B | 1200 mm |
| C | 1260 mm |
| F | 1160 mm |
| G | 1885 mm |
| E | 1335 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 1725 mm |
|---|---|
| Width | 1885 mm |
| Height | 1260 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.