EA-145AC7-C01 C
6.31 kW
Defrost: None
Product code: EA-140AG4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,310 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 39.1 m² |
| Inner volume | 8.4 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 55 kg |
| Quantity | 1 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 160 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-140AG4-C01 C | None |
|---|---|
| EA-140AG4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.57 | 2.60 | 2.63 | 2.67 | 2.68 | 2.68 | 2.66 | 2.75 | 2.94 | 3.20 | 3.14 | 3.13 | 3.11 | 3.09 |
| 5 | 3.26 | 3.33 | 3.41 | 3.48 | 3.51 | 3.50 | 3.48 | 3.55 | 3.78 | 4.10 | 3.99 | 3.95 | 3.90 | 3.81 |
| 6 | 3.92 | 4.06 | 4.19 | 4.30 | 4.35 | 4.36 | 4.33 | 4.39 | 4.66 | 5.05 | 4.89 | 4.83 | 4.73 | 4.58 |
| 7 | 4.57 | 4.77 | 4.96 | 5.12 | 5.20 | 5.24 | 5.21 | 5.27 | 5.58 | 6.04 | 5.83 | 5.75 | 5.62 | not rated |
| 8 | 5.14 | 5.43 | 5.70 | 5.93 | 6.06 | 6.12 | 6.09 | 6.16 | 6.52 | 7.04 | 6.81 | 6.70 | not rated | not rated |
| 9 | 5.65 | 6.02 | 6.36 | 6.66 | 6.85 | 6.92 | 6.94 | 7.02 | 7.44 | 8.05 | 7.79 | 7.66 | not rated | not rated |
| 10 | 6.11 | 6.57 | 7.00 | 7.32 | 7.57 | 7.71 | 7.75 | 7.84 | 8.31 | 8.99 | 8.73 | 8.60 | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.732 |
| SC2 | 0 | 8 | 6.155 |
| SC3 | -18 | 7 | 5.168 |
| SC4 | -25 | 6 | 4.185 |
| SC5 | -34 | 6 | 3.951 |
| A | 917 mm |
|---|---|
| B | 686 mm |
| C | 605 mm |
| F | 495 mm |
| E | 585 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 917 mm |
|---|---|
| Width | 686 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.