EA-163FC10-C19 C
10.87 kW
Defrost: Electric
Product code: EA-150AE7-C09 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,379 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 32.4 m² |
| Inner volume | 11.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 65 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 710 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-150AE7-C09 C | None |
|---|---|
| EA-150AE7-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.95 | 3.92 | 3.91 | 3.90 | 3.88 | 3.83 | 3.78 | 3.86 | 4.08 | 4.40 | 4.28 | 4.24 | 4.18 | 4.09 |
| 5 | 5.25 | 5.30 | 5.35 | 5.39 | 5.39 | 5.34 | 5.27 | 5.34 | 5.66 | 6.12 | 5.95 | 5.89 | 5.81 | 5.70 |
| 6 | 6.56 | 6.71 | 6.83 | 6.95 | 7.00 | 6.98 | 6.92 | 6.97 | 7.39 | 7.98 | 7.72 | 7.63 | 7.50 | 7.31 |
| 7 | 7.75 | 8.05 | 8.32 | 8.54 | 8.66 | 8.69 | 8.64 | 8.70 | 9.22 | 9.96 | 9.65 | 9.52 | 9.34 | 9.05 |
| 8 | 8.79 | 9.21 | 9.59 | 9.93 | 10.15 | 10.25 | 10.30 | 10.43 | 11.07 | 12.02 | 11.65 | 11.50 | 11.29 | 10.92 |
| 9 | 9.72 | 10.29 | 10.75 | 11.20 | 11.51 | 11.70 | 11.79 | 11.94 | 12.68 | 13.77 | 13.44 | 13.30 | 13.09 | 12.73 |
| 10 | 10.58 | 11.24 | 11.90 | 12.48 | 12.88 | 13.14 | 13.28 | 13.46 | 14.30 | 15.53 | 15.18 | 15.02 | 14.78 | 14.36 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 15.179 |
| SC2 | 0 | 8 | 10.426 |
| SC3 | -18 | 7 | 8.601 |
| SC4 | -25 | 6 | 6.830 |
| SC5 | -34 | 6 | 6.600 |
| A | 1237 mm |
|---|---|
| B | 640 mm |
| C | 685 mm |
| F | 445 mm |
| E | 885 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1237 mm |
|---|---|
| Width | 640 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.