EA-263EC10-C01 C
17.10 kW
Defrost: None
Product code: EA-163EG4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,794 m³/h |
|---|---|
| Air throw | 17 m |
| External surface | 133.5 m² |
| Inner volume | 26.1 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 148 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 75.9 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EA-163EG4-C01 C | None |
|---|---|
| EA-163EG4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.84 | 6.93 | 7.04 | 7.15 | 7.20 | 7.21 | 7.18 | 7.39 | 7.88 | 8.58 | 8.43 | 8.39 | 8.32 | 8.24 |
| 5 | 8.68 | 8.90 | 9.11 | 9.27 | 9.37 | 9.39 | 9.35 | 9.53 | 10.13 | 11.01 | 10.74 | 10.64 | 10.51 | 10.30 |
| 6 | 10.39 | 10.79 | 11.15 | 11.45 | 11.62 | 11.68 | 11.63 | 11.76 | 12.48 | 13.54 | 13.16 | 13.01 | 12.79 | 12.43 |
| 7 | 11.98 | 12.59 | 13.06 | 13.53 | 13.81 | 13.94 | 13.93 | 14.08 | 14.93 | 16.18 | 15.70 | 15.49 | 15.18 | 14.67 |
| 8 | 13.43 | 14.18 | 14.92 | 15.57 | 16.00 | 16.24 | 16.27 | 16.44 | 17.43 | 18.88 | 18.31 | 18.06 | 17.67 | 17.01 |
| 9 | 14.63 | 15.66 | 16.61 | 17.43 | 18.01 | 18.33 | 18.47 | 18.71 | 19.86 | 21.53 | 20.96 | 20.67 | 20.20 | 19.41 |
| 10 | ≈ 15.76 | 17.03 | 18.21 | 19.24 | 19.96 | 20.41 | 20.61 | 20.89 | 22.18 | 24.03 | 23.40 | 23.09 | 22.61 | 21.77 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 23.402 |
| SC2 | 0 | 8 | 16.443 |
| SC3 | -18 | 7 | 13.662 |
| SC4 | -25 | 6 | 11.147 |
| SC5 | -34 | 6 | 10.488 |
| A | 1215 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| E | 835 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 1215 mm |
|---|---|
| Width | 1100 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.