EA-163EG4-C01 C
17.10 kW
Defrost: None
Product code: EA-263EC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 18,106 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 65.1 m² |
| Inner volume | 27.5 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 167 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 77.6 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-263EC10-C01 C | None |
|---|---|
| EA-263EC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.65 | 6.49 | 6.40 | 6.35 | 6.29 | 6.23 | 6.17 | 6.21 | 6.57 | 7.09 | 6.92 | 6.86 | 6.77 | 6.64 |
| 5 | 8.92 | 8.79 | 8.71 | 8.67 | 8.60 | 8.51 | 8.41 | 8.45 | 8.95 | 9.66 | 9.40 | 9.31 | 9.17 | 8.96 |
| 6 | 11.26 | 11.19 | 11.16 | 11.17 | 11.12 | 11.02 | 10.89 | 10.91 | 11.54 | 12.44 | 12.07 | 11.94 | 11.75 | 11.47 |
| 7 | 13.52 | 13.59 | 13.68 | 13.77 | 13.77 | 13.68 | 13.55 | 13.55 | 14.33 | 15.45 | 14.97 | 14.79 | 14.53 | 14.13 |
| 8 | 15.70 | 15.94 | 16.18 | 16.40 | 16.48 | 16.44 | 16.33 | 16.31 | 17.25 | 18.61 | 18.03 | 17.80 | 17.47 | 16.96 |
| 9 | 17.76 | 18.16 | 18.58 | 18.95 | 19.15 | 19.20 | 19.14 | 19.16 | 20.28 | 21.90 | 21.23 | 20.96 | 20.57 | 19.94 |
| 10 | 19.55 | 20.20 | 20.82 | 21.39 | 21.77 | 21.99 | 21.99 | 22.06 | 23.36 | 25.25 | 24.52 | 24.22 | 23.77 | 23.05 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 24.517 |
| SC2 | 0 | 8 | 16.312 |
| SC3 | -18 | 7 | 13.782 |
| SC4 | -25 | 6 | 11.156 |
| SC5 | -34 | 6 | 11.260 |
| A | 2015 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 2015 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.