EA-335AG10-C01 C
13.06 kW
Defrost: None
Product code: EA-163FD10-C19 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 12,042 m³/h |
|---|---|
| Air throw | 28 m |
| External surface | 50.9 m² |
| Inner volume | 21.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 127 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 1,250 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 84.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EA-163FD10-C19 C | None |
|---|---|
| EA-163FD10-C19 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.92 | 4.87 | 4.85 | 4.84 | 4.81 | 4.77 | 4.73 | 4.73 | 5.00 | 5.40 | 5.26 | 5.21 | 5.13 | 5.02 |
| 5 | 6.52 | 6.52 | 6.55 | 6.59 | 6.58 | 6.54 | 6.48 | 6.48 | 6.86 | 7.40 | 7.19 | 7.11 | 7.01 | 6.84 |
| 6 | 8.06 | 8.19 | 8.32 | 8.43 | 8.47 | 8.44 | 8.39 | 8.39 | 8.88 | 9.58 | 9.30 | 9.20 | 9.05 | 8.81 |
| 7 | 9.50 | 9.80 | 10.06 | 10.28 | 10.39 | 10.40 | 10.38 | 10.40 | 11.00 | 11.88 | 11.54 | 11.41 | 11.22 | 10.92 |
| 8 | 10.85 | 11.27 | 11.69 | 12.05 | 12.27 | 12.39 | 12.42 | 12.47 | 13.21 | 14.28 | 13.90 | 13.75 | 13.52 | 13.15 |
| 9 | 12.00 | 12.62 | 13.19 | 13.70 | 14.05 | 14.29 | 14.43 | 14.56 | 15.45 | 16.73 | 16.32 | 16.15 | 15.89 | 15.47 |
| 10 | 13.05 | 13.86 | 14.59 | 15.25 | 15.71 | 16.03 | 16.23 | 16.41 | 17.44 | 18.95 | 18.58 | 18.42 | 18.19 | 17.79 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.42 | 4.36 | 4.33 | 4.33 | 4.31 | 4.28 | 4.24 | 4.27 | 4.52 | 4.89 | 4.77 | 4.73 | 4.67 | 4.58 |
| 5 | 5.82 | 5.81 | 5.82 | 5.84 | 5.83 | 5.80 | 5.75 | 5.77 | 6.11 | 6.60 | 6.43 | 6.36 | 6.27 | 6.14 |
| 6 | 7.23 | 7.30 | 7.37 | 7.43 | 7.45 | 7.43 | 7.38 | 7.39 | 7.82 | 8.45 | 8.21 | 8.12 | 7.99 | 7.80 |
| 7 | 8.57 | 8.75 | 8.91 | 9.06 | 9.13 | 9.14 | 9.09 | 9.11 | 9.64 | 10.41 | 10.11 | 10.00 | 9.83 | 9.57 |
| 8 | 9.82 | 10.14 | 10.43 | 10.68 | 10.79 | 10.85 | 10.84 | 10.87 | 11.51 | 12.45 | 12.09 | 11.96 | 11.75 | 11.42 |
| 9 | 10.99 | 11.42 | 11.85 | 12.22 | 12.46 | 12.58 | 12.62 | 12.68 | 13.43 | 14.54 | 14.15 | 13.99 | 13.76 | 13.37 |
| 10 | 11.97 | 12.61 | 13.17 | 13.67 | 14.02 | 14.25 | 14.38 | 14.50 | 15.37 | 16.65 | 16.24 | 16.07 | 15.80 | 15.37 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 18.577 | 16.241 |
| SC2 | 0 | 8 | 12.465 | 10.872 |
| SC3 | -18 | 7 | 10.337 | 9.098 |
| SC4 | -25 | 6 | 8.318 | 7.369 |
| SC5 | -34 | 6 | 8.096 | 7.258 |
| A | 1415 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E | 1035 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 1415 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.