EA-163EC7-C11 C
13.08 kW
Defrost: None
Product code: EA-163FC10-C13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 18,344 m³/h |
|---|---|
| Air throw | 42 m |
| External surface | 40.7 m² |
| Inner volume | 17.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 130 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EA-163FC10-C13 C | None |
|---|---|
| EA-163FC10-C13 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.79 | 4.68 | 4.61 | 4.56 | 4.50 | 4.43 | 4.37 | 4.35 | 4.59 | 4.94 | 4.80 | 4.75 | 4.68 | 4.58 |
| 5 | 6.52 | 6.44 | 6.40 | 6.37 | 6.30 | 6.22 | 6.13 | 6.10 | 6.43 | 6.91 | 6.69 | 6.61 | 6.49 | 6.32 |
| 6 | 8.22 | 8.27 | 8.30 | 8.34 | 8.29 | 8.22 | 8.11 | 8.07 | 8.52 | 9.16 | 8.86 | 8.75 | 8.59 | 8.35 |
| 7 | 9.85 | 10.05 | 10.22 | 10.35 | 10.39 | 10.33 | 10.24 | 10.20 | 10.78 | 11.60 | 11.22 | 11.08 | 10.87 | 10.55 |
| 8 | 11.38 | 11.71 | 12.04 | 12.31 | 12.46 | 12.49 | 12.45 | 12.44 | 13.16 | 14.19 | 13.74 | 13.57 | 13.32 | 12.92 |
| 9 | 12.63 | 13.15 | 13.63 | 14.07 | 14.35 | 14.52 | 14.61 | 14.72 | 15.60 | 16.86 | 16.38 | 16.18 | 15.90 | 15.43 |
| 10 | 13.81 | 14.52 | 15.17 | 15.74 | 16.12 | 16.37 | 16.52 | 16.65 | 17.68 | 19.18 | 18.77 | 18.60 | 18.35 | 17.93 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.28 | 4.17 | 4.11 | 4.07 | 4.03 | 3.98 | 3.94 | 3.93 | 4.16 | 4.49 | 4.37 | 4.33 | 4.27 | 4.18 |
| 5 | 5.78 | 5.70 | 5.65 | 5.62 | 5.57 | 5.50 | 5.43 | 5.42 | 5.73 | 6.17 | 5.99 | 5.92 | 5.83 | 5.69 |
| 6 | 7.31 | 7.29 | 7.29 | 7.29 | 7.25 | 7.19 | 7.10 | 7.08 | 7.48 | 8.05 | 7.80 | 7.71 | 7.58 | 7.39 |
| 7 | 8.79 | 8.88 | 8.96 | 9.04 | 9.04 | 8.99 | 8.91 | 8.88 | 9.38 | 10.10 | 9.78 | 9.66 | 9.49 | 9.22 |
| 8 | 10.20 | 10.42 | 10.62 | 10.76 | 10.84 | 10.84 | 10.78 | 10.76 | 11.38 | 12.27 | 11.88 | 11.74 | 11.52 | 11.18 |
| 9 | 11.52 | 11.85 | 12.19 | 12.49 | 12.65 | 12.72 | 12.70 | 12.71 | 13.45 | 14.52 | 14.09 | 13.92 | 13.66 | 13.25 |
| 10 | 12.60 | 13.12 | 13.59 | 14.02 | 14.30 | 14.48 | 14.58 | 14.68 | 15.55 | 16.82 | 16.35 | 16.16 | 15.87 | 15.40 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 18.769 | 16.349 |
| SC2 | 0 | 8 | 12.443 | 10.762 |
| SC3 | -18 | 7 | 10.378 | 9.048 |
| SC4 | -25 | 6 | 8.304 | 7.292 |
| SC5 | -34 | 6 | 8.244 | 7.319 |
| A | 1415 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| G | 1010 mm |
| E | 1035 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 1415 mm |
|---|---|
| Width | 1010 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.