EA-163FD10-C19 C
13.05 kW
Defrost: None
Product code: EA-335AG10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,263 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 41.9 m² |
| Inner volume | 19.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 94 kg |
| Quantity | 3 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 495 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | B |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-335AG10-C01 C | None |
|---|---|
| EA-335AG10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.99 | 5.00 | 5.03 | 5.06 | 5.06 | 5.03 | 4.97 | 5.10 | 5.44 | 5.89 | 5.77 | 5.73 | 5.67 | 5.56 |
| 5 | 6.48 | 6.58 | 6.69 | 6.79 | 6.82 | 6.80 | 6.74 | 6.86 | 7.28 | 7.89 | 7.67 | 7.59 | 7.48 | 7.33 |
| 6 | 7.89 | 8.12 | 8.34 | 8.53 | 8.63 | 8.65 | 8.60 | 8.70 | 9.23 | 10.00 | 9.68 | 9.56 | 9.39 | 9.10 |
| 7 | 9.29 | 9.65 | 9.99 | 10.29 | 10.44 | 10.52 | 10.50 | 10.61 | 11.24 | 12.18 | 11.80 | 11.64 | 11.41 | 11.02 |
| 8 | 10.53 | 11.06 | 11.54 | 11.97 | 12.26 | 12.39 | 12.41 | 12.54 | 13.30 | 14.40 | 13.96 | 13.78 | 13.49 | 12.99 |
| 9 | 11.64 | 12.31 | 12.94 | 13.51 | 13.82 | 14.06 | 14.17 | 14.37 | 15.26 | 16.56 | 16.15 | 15.94 | 15.61 | 15.01 |
| 10 | 12.64 | 13.50 | 14.30 | 14.91 | 15.40 | 15.72 | 15.87 | 16.12 | 17.12 | 18.57 | 18.14 | 17.93 | 17.59 | 16.97 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 18.141 |
| SC2 | 0 | 8 | 12.541 |
| SC3 | -18 | 7 | 10.370 |
| SC4 | -25 | 6 | 8.338 |
| SC5 | -34 | 6 | 7.952 |
| A | 1857 mm |
|---|---|
| B | 673 mm |
| C | 525 mm |
| F | 495 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1857 mm |
|---|---|
| Width | 623 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.