EA-230AC6-C05 C
3.64 kW
Defrost: Electric
Product code: EA-230AC7-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,581 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 12.6 m² |
| Inner volume | 3.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 33 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 67.1 dB(A) |
| Energy class | C |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø22 |
| EA-230AC7-C01 C | None |
|---|---|
| EA-230AC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.37 | 1.33 | 1.31 | 1.30 | 1.28 | 1.27 | 1.26 | 1.28 | 1.35 | 1.46 | 1.43 | 1.42 | 1.40 | 1.38 |
| 5 | 1.87 | 1.83 | 1.81 | 1.80 | 1.78 | 1.75 | 1.73 | 1.74 | 1.85 | 2.00 | 1.95 | 1.93 | 1.91 | 1.87 |
| 6 | 2.40 | 2.37 | 2.36 | 2.35 | 2.33 | 2.30 | 2.26 | 2.27 | 2.41 | 2.59 | 2.51 | 2.49 | 2.45 | 2.40 |
| 7 | 2.92 | 2.92 | 2.93 | 2.93 | 2.92 | 2.89 | 2.85 | 2.86 | 3.02 | 3.25 | 3.14 | 3.10 | 3.05 | 2.96 |
| 8 | 3.45 | 3.48 | 3.51 | 3.54 | 3.54 | 3.52 | 3.48 | 3.48 | 3.68 | 3.96 | 3.82 | 3.77 | 3.69 | 3.57 |
| 9 | 3.94 | 4.02 | 4.09 | 4.15 | 4.18 | 4.17 | 4.14 | 4.13 | 4.37 | 4.71 | 4.55 | 4.49 | 4.39 | 4.24 |
| 10 | 4.38 | 4.49 | 4.61 | 4.72 | 4.78 | 4.82 | 4.80 | 4.81 | 5.08 | 5.49 | 5.31 | 5.23 | 5.12 | 4.94 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.308 |
| SC2 | 0 | 8 | 3.480 |
| SC3 | -18 | 7 | 2.931 |
| SC4 | -25 | 6 | 2.355 |
| SC5 | -34 | 6 | 2.394 |
| A | 1157 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 418 mm |
| E | 835 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø22 |
| Length | 1157 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |