EA-335AG6-C01 C
14.56 kW
Defrost: None
Product code: EA-535AC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 12,787 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 34.9 m² |
| Inner volume | 16.1 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 101 kg |
| Quantity | 5 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 825 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 77.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-535AC10-C01 C | None |
|---|---|
| EA-535AC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.22 | 5.17 | 5.14 | 5.12 | 5.07 | 5.01 | 4.94 | 4.98 | 5.25 | 5.65 | 5.49 | 5.42 | 5.34 | 5.21 |
| 5 | 6.99 | 7.03 | 7.08 | 7.14 | 7.13 | 7.08 | 7.01 | 7.05 | 7.46 | 8.05 | 7.82 | 7.73 | 7.62 | 7.44 |
| 6 | 8.75 | 8.92 | 9.06 | 9.23 | 9.30 | 9.30 | 9.25 | 9.30 | 9.86 | 10.64 | 10.32 | 10.21 | 10.04 | 9.79 |
| 7 | 10.37 | 10.72 | 11.05 | 11.34 | 11.52 | 11.60 | 11.58 | 11.67 | 12.37 | 13.39 | 13.02 | 12.87 | 12.65 | 12.31 |
| 8 | 11.79 | 12.29 | 12.76 | 13.21 | 13.51 | 13.69 | 13.81 | 13.99 | 14.87 | 16.17 | 15.78 | 15.62 | 15.37 | 14.96 |
| 9 | 13.08 | 13.76 | 14.34 | 14.92 | 15.34 | 15.64 | 15.82 | 16.04 | 17.06 | 18.55 | 18.19 | 18.04 | 17.81 | 17.40 |
| 10 | 14.28 | 15.09 | 15.90 | 16.64 | 17.19 | 17.58 | 17.83 | 18.10 | 19.26 | 20.95 | 20.57 | 20.40 | 20.14 | 19.67 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 20.570 |
| SC2 | 0 | 8 | 13.989 |
| SC3 | -18 | 7 | 11.424 |
| SC4 | -25 | 6 | 9.063 |
| SC5 | -34 | 6 | 8.795 |
| A | 2857 mm |
|---|---|
| B | 523 mm |
| C | 525 mm |
| F | 345 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 2535 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2857 mm |
|---|---|
| Width | 523 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.