EA-163EG10-C01 C
13.29 kW
Defrost: Electric
Product code: EA-340AC7-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,698 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 36.7 m² |
| Inner volume | 12.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 81 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-340AC7-C01 C | None |
|---|---|
| EA-340AC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.79 | 4.74 | 4.71 | 4.69 | 4.65 | 4.60 | 4.54 | 4.59 | 4.85 | 5.23 | 5.09 | 5.04 | 4.97 | 4.86 |
| 5 | 6.43 | 6.46 | 6.50 | 6.54 | 6.52 | 6.47 | 6.39 | 6.44 | 6.83 | 7.37 | 7.16 | 7.09 | 6.99 | 6.84 |
| 6 | 8.06 | 8.22 | 8.37 | 8.48 | 8.53 | 8.51 | 8.44 | 8.50 | 9.00 | 9.71 | 9.41 | 9.31 | 9.16 | 8.93 |
| 7 | 9.55 | 9.86 | 10.16 | 10.44 | 10.60 | 10.65 | 10.61 | 10.68 | 11.31 | 12.23 | 11.86 | 11.72 | 11.51 | 11.18 |
| 8 | 10.83 | 11.29 | 11.72 | 12.06 | 12.33 | 12.49 | 12.57 | 12.72 | 13.52 | 14.68 | 14.35 | 14.22 | 14.01 | 13.61 |
| 9 | 12.01 | 12.64 | 13.16 | 13.69 | 14.05 | 14.29 | 14.42 | 14.60 | 15.51 | 16.85 | 16.49 | 16.34 | 16.11 | 15.71 |
| 10 | 13.10 | 13.86 | 14.60 | 15.28 | 15.76 | 16.07 | 16.26 | 16.49 | 17.53 | 19.05 | 18.66 | 18.49 | 18.22 | 17.75 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 18.659 |
| SC2 | 0 | 8 | 12.722 |
| SC3 | -18 | 7 | 10.520 |
| SC4 | -25 | 6 | 8.370 |
| SC5 | -34 | 6 | 8.106 |
| A | 2017 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 1685 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 2017 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.