EA-150AG6-C10 C
13.15 kW
Defrost: None
Product code: EA-530AE6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,703 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 55.8 m² |
| Inner volume | 15.4 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 83 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 310 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 50.0 dB(A) |
|---|---|
| Sound power | 72.4 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-530AE6-C01 C | None |
|---|---|
| EA-530AE6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.09 | 5.13 | 5.18 | 5.23 | 5.24 | 5.23 | 5.19 | 5.32 | 5.67 | 6.15 | 6.03 | 5.99 | 5.94 | 5.87 |
| 5 | 6.55 | 6.69 | 6.82 | 6.95 | 7.00 | 7.00 | 6.95 | 7.07 | 7.51 | 8.15 | 7.93 | 7.85 | 7.74 | 7.59 |
| 6 | 7.98 | 8.24 | 8.49 | 8.69 | 8.81 | 8.85 | 8.81 | 8.92 | 9.46 | 10.26 | 9.95 | 9.83 | 9.66 | 9.38 |
| 7 | 9.28 | 9.69 | 10.08 | 10.42 | 10.64 | 10.73 | 10.72 | 10.83 | 11.49 | 12.45 | 12.07 | 11.92 | 11.69 | 11.29 |
| 8 | 10.41 | 10.98 | 11.50 | 11.96 | 12.22 | 12.40 | 12.48 | 12.65 | 13.43 | 14.58 | 14.22 | 14.05 | 13.77 | 13.25 |
| 9 | 11.46 | 12.19 | 12.80 | 13.39 | 13.80 | 14.06 | 14.18 | 14.38 | 15.27 | 16.56 | 16.17 | 15.98 | 15.68 | 15.12 |
| 10 | 12.41 | 13.25 | 14.09 | 14.84 | 15.36 | 15.70 | 15.87 | 16.11 | 17.11 | 18.56 | 18.13 | 17.92 | 17.57 | 16.93 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 18.134 |
| SC2 | 0 | 8 | 12.650 |
| SC3 | -18 | 7 | 10.523 |
| SC4 | -25 | 6 | 8.491 |
| SC5 | -34 | 6 | 8.047 |
| A | 2407 mm |
|---|---|
| B | 573 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 428 mm |
| E2 | 410 mm |
| E | 2085 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 2407 mm |
|---|---|
| Width | 573 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.