EA-530AC8-C01 C
9.19 kW
Defrost: None
Product code: EA-430AC6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,247 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 32.0 m² |
| Inner volume | 9.4 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 61 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.1 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-430AC6-C01 C | None |
|---|---|
| EA-430AC6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.45 | 3.44 | 3.44 | 3.46 | 3.45 | 3.44 | 3.41 | 3.48 | 3.70 | 4.00 | 3.92 | 3.88 | 3.84 | 3.77 |
| 5 | 4.54 | 4.58 | 4.64 | 4.69 | 4.70 | 4.69 | 4.66 | 4.72 | 5.01 | 5.43 | 5.29 | 5.24 | 5.18 | 5.09 |
| 6 | 5.62 | 5.74 | 5.86 | 5.96 | 6.02 | 6.03 | 6.00 | 6.06 | 6.43 | 6.96 | 6.76 | 6.69 | 6.59 | 6.43 |
| 7 | 6.61 | 6.85 | 7.07 | 7.26 | 7.37 | 7.42 | 7.40 | 7.47 | 7.92 | 8.58 | 8.34 | 8.25 | 8.11 | 7.89 |
| 8 | 7.48 | 7.81 | 8.11 | 8.39 | 8.56 | 8.68 | 8.73 | 8.85 | 9.40 | 10.21 | 9.97 | 9.86 | 9.70 | 9.42 |
| 9 | 8.28 | 8.72 | 9.09 | 9.46 | 9.72 | 9.88 | 9.97 | 10.10 | 10.73 | 11.66 | 11.41 | 11.31 | 11.14 | 10.86 |
| 10 | 9.02 | 9.54 | 10.06 | 10.53 | 10.85 | 11.07 | 11.20 | 11.36 | 12.08 | 13.12 | 12.86 | 12.73 | 12.55 | 12.23 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.856 |
| SC2 | 0 | 8 | 8.846 |
| SC3 | -18 | 7 | 7.313 |
| SC4 | -25 | 6 | 5.863 |
| SC5 | -34 | 6 | 5.650 |
| A | 2107 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 455 mm |
| E2 | 438 mm |
| E | 1785 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2107 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.