EA-430AE10-C01 C
9.21 kW
Defrost: None
Product code: EA-430AC4-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,361 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 44.4 m² |
| Inner volume | 9.5 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 50 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø28 |
| EA-430AC4-C05 C | None |
|---|---|
| EA-430AC4-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.48 | 3.57 | 3.65 | 3.73 | 3.76 | 3.77 | 3.75 | 3.86 | 4.12 | 4.48 | 4.41 | 4.38 | 4.35 | 4.30 |
| 5 | 4.45 | 4.63 | 4.80 | 4.93 | 5.01 | 5.04 | 5.03 | 5.14 | 5.47 | 5.94 | 5.80 | 5.75 | 5.67 | 5.57 |
| 6 | 5.33 | 5.62 | 5.88 | 6.12 | 6.27 | 6.36 | 6.38 | 6.47 | 6.87 | 7.47 | 7.27 | 7.19 | 7.08 | 6.89 |
| 7 | 6.07 | 6.48 | 6.85 | 7.13 | 7.35 | 7.49 | 7.55 | 7.69 | 8.18 | 8.91 | 8.70 | 8.61 | 8.48 | 8.26 |
| 8 | 6.75 | 7.20 | 7.70 | 8.13 | 8.44 | 8.63 | 8.73 | 8.89 | 9.45 | 10.28 | 10.05 | 9.94 | 9.78 | 9.50 |
| 9 | ≈ 7.36 | 7.95 | 8.56 | 9.10 | 9.49 | 9.76 | 9.90 | 10.09 | 10.73 | 11.67 | 11.42 | 11.29 | 11.10 | 10.76 |
| 10 | ≈ 7.68 | 8.63 | 9.36 | 10.03 | 10.52 | 10.87 | 11.07 | 11.30 | 12.02 | 13.07 | 12.80 | 12.66 | 12.44 | 12.05 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.798 |
| SC2 | 0 | 8 | 8.890 |
| SC3 | -18 | 7 | 7.228 |
| SC4 | -25 | 6 | 5.884 |
| SC5 | -34 | 6 | 5.398 |
| A | 2107 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 455 mm |
| E2 | 437.5 mm |
| E | 1785 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø28 |
| Length | 2107 mm |
|---|---|
| Width | 517 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.