EA-330AE7-C01 C
7.66 kW
Defrost: Electric
Product code: EA-430AC8-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,433 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 24.7 m² |
| Inner volume | 9.4 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 61 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.2 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-430AC8-C01 C | None |
|---|---|
| EA-430AC8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.84 | 2.79 | 2.77 | 2.76 | 2.75 | 2.72 | 2.69 | 2.74 | 2.89 | 3.13 | 3.05 | 3.02 | 2.98 | 2.93 |
| 5 | 3.79 | 3.78 | 3.79 | 3.80 | 3.79 | 3.76 | 3.72 | 3.76 | 3.99 | 4.31 | 4.20 | 4.16 | 4.11 | 4.03 |
| 6 | 4.74 | 4.79 | 4.84 | 4.90 | 4.91 | 4.89 | 4.85 | 4.89 | 5.18 | 5.60 | 5.43 | 5.37 | 5.29 | 5.17 |
| 7 | 5.68 | 5.80 | 5.91 | 6.01 | 6.07 | 6.08 | 6.05 | 6.09 | 6.45 | 6.97 | 6.76 | 6.68 | 6.57 | 6.38 |
| 8 | 6.56 | 6.76 | 6.96 | 7.14 | 7.24 | 7.29 | 7.28 | 7.33 | 7.76 | 8.41 | 8.17 | 8.07 | 7.93 | 7.69 |
| 9 | 7.33 | 7.61 | 7.89 | 8.14 | 8.32 | 8.43 | 8.47 | 8.57 | 9.10 | 9.86 | 9.60 | 9.49 | 9.32 | 9.05 |
| 10 | 8.03 | 8.42 | 8.78 | 9.08 | 9.30 | 9.46 | 9.55 | 9.67 | 10.27 | 11.16 | 10.93 | 10.82 | 10.67 | 10.40 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.928 |
| SC2 | 0 | 8 | 7.326 |
| SC3 | -18 | 7 | 6.039 |
| SC4 | -25 | 6 | 4.840 |
| SC5 | -34 | 6 | 4.756 |
| A | 2107 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 455 mm |
| E2 | 438 mm |
| E | 1785 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2107 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.