EA-163GD7-C19 C
18.59 kW
Defrost: Electric
Product code: EA-440AC6-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 12,725 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 56.1 m² |
| Inner volume | 16.1 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 104 kg |
| Quantity | 4 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 640 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-440AC6-C01 C | None |
|---|---|
| EA-440AC6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.82 | 6.79 | 6.77 | 6.77 | 6.73 | 6.67 | 6.59 | 6.68 | 7.06 | 7.62 | 7.42 | 7.35 | 7.25 | 7.10 |
| 5 | 9.09 | 9.20 | 9.30 | 9.39 | 9.40 | 9.34 | 9.24 | 9.33 | 9.90 | 10.69 | 10.40 | 10.30 | 10.16 | 9.95 |
| 6 | 11.33 | 11.63 | 11.91 | 12.15 | 12.25 | 12.24 | 12.16 | 12.26 | 12.99 | 14.03 | 13.62 | 13.46 | 13.25 | 12.93 |
| 7 | 13.24 | 13.74 | 14.21 | 14.64 | 14.92 | 15.04 | 15.11 | 15.31 | 16.25 | 17.58 | 17.09 | 16.89 | 16.61 | 16.16 |
| 8 | 14.96 | 15.68 | 16.27 | 16.87 | 17.28 | 17.54 | 17.66 | 17.89 | 19.01 | 20.65 | 20.20 | 20.02 | 19.73 | 19.26 |
| 9 | 16.55 | 17.43 | 18.32 | 19.11 | 19.67 | 20.03 | 20.24 | 20.51 | 21.79 | 23.69 | 23.18 | 22.95 | 22.61 | 22.03 |
| 10 | 17.92 | 19.14 | 20.28 | 21.29 | 22.01 | 22.51 | 22.80 | 23.14 | 24.60 | 26.75 | 26.19 | 25.93 | 25.54 | 24.84 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 26.193 |
| SC2 | 0 | 8 | 17.889 |
| SC3 | -18 | 7 | 14.765 |
| SC4 | -25 | 6 | 11.910 |
| SC5 | -34 | 6 | 11.410 |
| A | 2567 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 2235 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2567 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.