EA-HL-250AC4-A10 C
26.11 kW
Defrost: None
Product code: EA-HL-250AE10-A10 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 15,500 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 69.8 m² |
| Inner volume | 32.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 167 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 1,380 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.7 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-HL-250AE10-A10 C | None |
|---|---|
| EA-HL-250AE10-A10 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.62 | 9.56 | 9.55 | 9.57 | 9.53 | 9.46 | 9.36 | 9.42 | 9.98 | 10.77 | 10.47 | 10.36 | 10.20 | 9.97 |
| 5 | 12.66 | 12.78 | 12.92 | 13.06 | 13.10 | 13.06 | 12.97 | 13.03 | 13.80 | 14.91 | 14.49 | 14.34 | 14.13 | 13.82 |
| 6 | 15.68 | 15.95 | 16.30 | 16.62 | 16.80 | 16.85 | 16.81 | 16.89 | 17.90 | 19.35 | 18.81 | 18.61 | 18.31 | 17.84 |
| 7 | 18.47 | 19.09 | 19.69 | 20.23 | 20.57 | 20.72 | 20.76 | 20.90 | 22.16 | 24.00 | 23.37 | 23.12 | 22.74 | 22.14 |
| 8 | 21.00 | 21.90 | 22.77 | 23.57 | 24.14 | 24.52 | 24.71 | 24.94 | 26.45 | 28.70 | 28.02 | 27.74 | 27.31 | 26.60 |
| 9 | 23.24 | 24.47 | 25.62 | 26.55 | 27.31 | 27.84 | 28.19 | 28.57 | 30.37 | 33.03 | 32.42 | 32.15 | 31.74 | 31.04 |
| 10 | 25.32 | 26.90 | 28.22 | 29.53 | 30.51 | 31.20 | 31.67 | 32.14 | 34.19 | 37.20 | 36.55 | 36.25 | 35.80 | 35.01 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.49 | 8.41 | 8.38 | 8.39 | 8.36 | 8.30 | 8.22 | 8.32 | 8.83 | 9.55 | 9.32 | 9.23 | 9.10 | 8.91 |
| 5 | 11.18 | 11.20 | 11.27 | 11.36 | 11.38 | 11.34 | 11.25 | 11.33 | 12.02 | 13.00 | 12.64 | 12.52 | 12.35 | 12.10 |
| 6 | 13.80 | 13.99 | 14.21 | 14.42 | 14.53 | 14.54 | 14.47 | 14.56 | 15.43 | 16.69 | 16.22 | 16.04 | 15.78 | 15.38 |
| 7 | 16.40 | 16.78 | 17.12 | 17.50 | 17.73 | 17.82 | 17.81 | 17.92 | 18.99 | 20.56 | 19.98 | 19.76 | 19.42 | 18.87 |
| 8 | 18.78 | 19.42 | 20.03 | 20.60 | 20.96 | 21.14 | 21.19 | 21.35 | 22.64 | 24.52 | 23.89 | 23.62 | 23.22 | 22.55 |
| 9 | 20.97 | 21.85 | 22.69 | 23.48 | 24.03 | 24.40 | 24.60 | 24.79 | 26.29 | 28.51 | 27.83 | 27.53 | 27.07 | 26.30 |
| 10 | 22.93 | 24.09 | 25.18 | 26.17 | 26.80 | 27.29 | 27.60 | 27.97 | 29.72 | 32.29 | 31.67 | 31.37 | 30.93 | 30.11 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 36.549 | 31.665 |
| SC2 | 0 | 8 | 24.938 | 21.348 |
| SC3 | -18 | 7 | 20.384 | 17.611 |
| SC4 | -25 | 6 | 16.299 | 14.206 |
| SC5 | -34 | 6 | 15.774 | 13.856 |
| A | 2387 mm |
|---|---|
| B | 640 mm |
| C | 875 mm |
| F | 560 mm |
| E1 | 1018 mm |
| E | 2035 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2387 mm |
|---|---|
| Width | 640 mm |
| Height | 875 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.