EB-325AC4-B05 C
4.85 kW
Defrost: None
Product code: EB-140AC6-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,459 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 13.8 m² |
| Inner volume | 3.4 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 37 kg |
| Quantity | 1 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 160 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EB-140AC6-B01 C | None |
|---|---|
| EB-140AC6-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.79 | 1.79 | 1.79 | 1.80 | 1.80 | 1.79 | 1.77 | 1.79 | 1.89 | 2.05 | 1.99 | 1.98 | 1.95 | 1.91 |
| 5 | 2.37 | 2.41 | 2.45 | 2.48 | 2.49 | 2.49 | 2.47 | 2.49 | 2.64 | 2.85 | 2.78 | 2.75 | 2.71 | 2.66 |
| 6 | 2.92 | 3.02 | 3.11 | 3.18 | 3.23 | 3.24 | 3.24 | 3.26 | 3.46 | 3.74 | 3.63 | 3.59 | 3.54 | 3.45 |
| 7 | 3.39 | 3.54 | 3.68 | 3.80 | 3.89 | 3.94 | 3.97 | 4.02 | 4.27 | 4.64 | 4.55 | 4.51 | 4.44 | 4.32 |
| 8 | 3.86 | 4.06 | 4.24 | 4.39 | 4.51 | 4.59 | 4.64 | 4.70 | 4.99 | 5.43 | 5.32 | 5.27 | 5.20 | 5.09 |
| 9 | 4.27 | 4.53 | 4.78 | 4.99 | 5.15 | 5.25 | 5.31 | 5.38 | 5.72 | 6.22 | 6.10 | 6.05 | 5.97 | 5.83 |
| 10 | 4.65 | 4.98 | 5.29 | 5.56 | 5.76 | 5.90 | 5.99 | 6.06 | 6.45 | 7.01 | 6.89 | 6.83 | 6.74 | 6.59 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.886 |
| SC2 | 0 | 8 | 4.696 |
| SC3 | -18 | 7 | 3.838 |
| SC4 | -25 | 6 | 3.105 |
| SC5 | -34 | 6 | 2.943 |
| A | 1017 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E | 685 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 1017 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.