EB-335AC4-B01 C
12.96 kW
Defrost: None
Product code: EB-245AC4-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,711 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 38.4 m² |
| Inner volume | 6.9 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 71 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | E |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-245AC4-B01 C | None |
|---|---|
| EB-245AC4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.92 | 4.89 | 4.88 | 4.87 | 4.84 | 4.79 | 4.73 | 4.82 | 5.10 | 5.50 | 5.37 | 5.32 | 5.25 | 5.15 |
| 5 | 6.61 | 6.70 | 6.77 | 6.83 | 6.83 | 6.77 | 6.68 | 6.79 | 7.21 | 7.79 | 7.58 | 7.51 | 7.42 | 7.26 |
| 6 | 8.10 | 8.32 | 8.52 | 8.71 | 8.82 | 8.87 | 8.87 | 9.00 | 9.54 | 10.31 | 10.00 | 9.89 | 9.73 | 9.50 |
| 7 | 9.50 | 9.84 | 10.15 | 10.40 | 10.58 | 10.66 | 10.67 | 10.83 | 11.51 | 12.48 | 12.19 | 12.08 | 11.92 | 11.67 |
| 8 | 10.77 | 11.27 | 11.72 | 12.12 | 12.37 | 12.50 | 12.52 | 12.69 | 13.48 | 14.63 | 14.27 | 14.13 | 13.92 | 13.59 |
| 9 | 11.95 | 12.63 | 13.25 | 13.79 | 14.14 | 14.34 | 14.42 | 14.57 | 15.47 | 16.79 | 16.38 | 16.21 | 15.96 | 15.55 |
| 10 | 13.03 | 13.92 | 14.72 | 15.42 | 15.83 | 16.12 | 16.26 | 16.48 | 17.51 | 19.01 | 18.56 | 18.36 | 18.06 | 17.57 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 18.555 |
| SC2 | 0 | 8 | 12.689 |
| SC3 | -18 | 7 | 10.482 |
| SC4 | -25 | 6 | 8.521 |
| SC5 | -34 | 6 | 8.159 |
| A | 1667 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E | 1335 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1667 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.