EB-240AE6-B01 C
12.88 kW
Defrost: None
Product code: EB-335AC4-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,763 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 47.0 m² |
| Inner volume | 7.8 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 70 kg |
| Quantity | 3 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 495 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-335AC4-B01 C | None |
|---|---|
| EB-335AC4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.84 | 4.95 | 5.06 | 5.16 | 5.20 | 5.21 | 5.19 | 5.27 | 5.60 | 6.07 | 5.94 | 5.89 | 5.82 | 5.70 |
| 5 | 6.19 | 6.44 | 6.68 | 6.90 | 7.04 | 7.13 | 7.15 | 7.24 | 7.70 | 8.34 | 8.15 | 8.07 | 7.97 | 7.81 |
| 6 | 7.34 | 7.73 | 8.09 | 8.42 | 8.64 | 8.78 | 8.86 | 9.00 | 9.58 | 10.42 | 10.22 | 10.14 | 10.03 | 9.85 |
| 7 | 8.47 | 9.01 | 9.51 | 9.95 | 10.26 | 10.47 | 10.58 | 10.74 | 11.43 | 12.44 | 12.20 | 12.10 | 11.94 | 11.70 |
| 8 | 9.44 | 10.16 | 10.83 | 11.42 | 11.85 | 12.14 | 12.27 | 12.48 | 13.28 | 14.45 | 14.19 | 14.08 | 13.90 | 13.60 |
| 9 | ≈ 10.33 | 11.24 | 12.09 | 12.75 | 13.32 | 13.71 | 13.98 | 14.24 | 15.16 | 16.51 | 16.24 | 16.10 | 15.90 | 15.53 |
| 10 | ≈ 11.12 | 12.23 | 13.16 | 14.09 | 14.80 | 15.32 | 15.67 | 15.99 | 17.04 | 18.57 | 18.29 | 18.15 | 17.92 | 17.51 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 18.291 |
| SC2 | 0 | 8 | 12.478 |
| SC3 | -18 | 7 | 10.090 |
| SC4 | -25 | 6 | 8.092 |
| SC5 | -34 | 6 | 7.429 |
| A | 2157 mm |
|---|---|
| B | 520 mm |
| C | 553 mm |
| F | 345 mm |
| E1 | 618 mm |
| E2 | 600 mm |
| E | 1835 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2157 mm |
|---|---|
| Width | 520 mm |
| Height | 553 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.