EB-430BE7-B01 C
11.20 kW
Defrost: None
Product code: EB-245AC7-B07 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 10,814 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 24.2 m² |
| Inner volume | 6.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 71 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,360 rpm |
| Power | 960 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | E |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-245AC7-B07 C | None |
|---|---|
| EB-245AC7-B07 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.99 | 3.90 | 3.84 | 3.80 | 3.74 | 3.67 | 3.60 | 3.61 | 3.81 | 4.10 | 3.97 | 3.93 | 3.86 | 3.77 |
| 5 | 5.50 | 5.48 | 5.46 | 5.45 | 5.40 | 5.32 | 5.22 | 5.24 | 5.54 | 5.96 | 5.76 | 5.69 | 5.58 | 5.43 |
| 6 | 6.98 | 7.08 | 7.16 | 7.23 | 7.23 | 7.18 | 7.08 | 7.10 | 7.50 | 8.08 | 7.79 | 7.69 | 7.56 | 7.36 |
| 7 | 8.24 | 8.44 | 8.65 | 8.84 | 8.95 | 9.01 | 9.01 | 9.10 | 9.63 | 10.39 | 10.04 | 9.91 | 9.72 | 9.43 |
| 8 | 9.47 | 9.78 | 10.07 | 10.32 | 10.49 | 10.59 | 10.62 | 10.73 | 11.39 | 12.35 | 12.05 | 11.93 | 11.76 | 11.48 |
| 9 | 10.58 | 11.03 | 11.44 | 11.81 | 12.06 | 12.19 | 12.26 | 12.38 | 13.15 | 14.27 | 13.92 | 13.78 | 13.57 | 13.24 |
| 10 | 11.62 | 12.22 | 12.78 | 13.27 | 13.61 | 13.82 | 13.92 | 14.06 | 14.93 | 16.20 | 15.81 | 15.65 | 15.42 | 15.02 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.51 | 3.43 | 3.37 | 3.34 | 3.30 | 3.25 | 3.20 | 3.24 | 3.42 | 3.69 | 3.59 | 3.55 | 3.50 | 3.43 |
| 5 | 4.81 | 4.76 | 4.74 | 4.72 | 4.68 | 4.61 | 4.54 | 4.57 | 4.85 | 5.22 | 5.07 | 5.02 | 4.94 | 4.82 |
| 6 | 6.12 | 6.14 | 6.18 | 6.22 | 6.20 | 6.14 | 6.06 | 6.09 | 6.44 | 6.94 | 6.71 | 6.63 | 6.52 | 6.36 |
| 7 | 7.37 | 7.50 | 7.64 | 7.75 | 7.79 | 7.77 | 7.70 | 7.73 | 8.17 | 8.81 | 8.52 | 8.40 | 8.24 | 8.00 |
| 8 | 8.44 | 8.65 | 8.87 | 9.08 | 9.21 | 9.28 | 9.30 | 9.39 | 9.97 | 10.81 | 10.46 | 10.33 | 10.13 | 9.81 |
| 9 | 9.51 | 9.82 | 10.12 | 10.38 | 10.56 | 10.67 | 10.71 | 10.81 | 11.48 | 12.45 | 12.15 | 12.03 | 11.84 | 11.54 |
| 10 | 10.49 | 10.91 | 11.32 | 11.69 | 11.93 | 12.07 | 12.14 | 12.26 | 13.01 | 14.12 | 13.79 | 13.64 | 13.43 | 13.07 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 15.810 | 13.786 |
| SC2 | 0 | 8 | 10.729 | 9.390 |
| SC3 | -18 | 7 | 8.891 | 7.777 |
| SC4 | -25 | 6 | 7.161 | 6.180 |
| SC5 | -34 | 6 | 7.013 | 6.133 |
| A | 1667 mm |
|---|---|
| B | 560 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E | 1335 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1667 mm |
|---|---|
| Width | 560 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.