EB-245AC7-B07 C
11.19 kW
Defrost: None
Product code: EB-430BE7-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,123 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 37.2 m² |
| Inner volume | 10.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 68 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.2 dB(A) |
| Energy class | A |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-430BE7-B01 C | None |
|---|---|
| EB-430BE7-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.36 | 4.40 | 4.46 | 4.52 | 4.54 | 4.54 | 4.52 | 4.61 | 4.91 | 5.32 | 5.21 | 5.18 | 5.13 | 5.06 |
| 5 | 5.59 | 5.72 | 5.85 | 5.97 | 6.04 | 6.07 | 6.05 | 6.13 | 6.51 | 7.07 | 6.88 | 6.82 | 6.72 | 6.57 |
| 6 | 6.75 | 6.99 | 7.22 | 7.43 | 7.56 | 7.63 | 7.64 | 7.72 | 8.20 | 8.90 | 8.66 | 8.57 | 8.43 | 8.20 |
| 7 | 7.81 | 8.15 | 8.49 | 8.79 | 9.00 | 9.14 | 9.20 | 9.33 | 9.91 | 10.77 | 10.50 | 10.38 | 10.21 | 9.91 |
| 8 | 8.76 | 9.24 | 9.68 | 10.09 | 10.36 | 10.55 | 10.64 | 10.80 | 11.47 | 12.46 | 12.19 | 12.07 | 11.89 | 11.56 |
| 9 | 9.73 | 10.33 | 10.89 | 11.39 | 11.74 | 11.95 | 12.09 | 12.27 | 13.04 | 14.17 | 13.87 | 13.73 | 13.52 | 13.14 |
| 10 | 10.56 | 11.31 | 12.01 | 12.62 | 13.07 | 13.38 | 13.55 | 13.75 | 14.62 | 15.88 | 15.54 | 15.39 | 15.14 | 14.71 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 15.541 |
| SC2 | 0 | 8 | 10.795 |
| SC3 | -18 | 7 | 8.885 |
| SC4 | -25 | 6 | 7.223 |
| SC5 | -34 | 6 | 6.812 |
| A | 2357 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2357 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.