EB-130BE4-B01 C
3.06 kW
Defrost: Electric
Product code: EB-325AA4-B05 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,646 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 10.2 m² |
| Inner volume | 1.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 29 kg |
| Quantity | 3 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 285 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 42.0 dB(A) |
|---|---|
| Sound power | 63.5 dB(A) |
| Energy class | E |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø15,9 |
| EB-325AA4-B05 C | None |
|---|---|
| EB-325AA4-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.14 | 1.13 | 1.12 | 1.12 | 1.12 | 1.11 | 1.11 | 1.12 | 1.18 | 1.28 | 1.25 | 1.24 | 1.22 | 1.20 |
| 5 | 1.52 | 1.53 | 1.54 | 1.56 | 1.56 | 1.55 | 1.54 | 1.55 | 1.64 | 1.78 | 1.73 | 1.72 | 1.69 | 1.66 |
| 6 | 1.89 | 1.93 | 1.97 | 2.01 | 2.03 | 2.04 | 2.03 | 2.04 | 2.16 | 2.34 | 2.28 | 2.25 | 2.22 | 2.17 |
| 7 | 2.20 | 2.27 | 2.33 | 2.40 | 2.44 | 2.46 | 2.48 | 2.51 | 2.66 | 2.89 | 2.83 | 2.81 | 2.78 | 2.73 |
| 8 | 2.52 | 2.62 | 2.70 | 2.79 | 2.84 | 2.88 | 2.90 | 2.93 | 3.12 | 3.39 | 3.32 | 3.29 | 3.25 | 3.19 |
| 9 | 2.81 | 2.94 | 3.06 | 3.17 | 3.25 | 3.30 | 3.34 | 3.37 | 3.58 | 3.89 | 3.82 | 3.78 | 3.74 | 3.66 |
| 10 | 3.07 | 3.25 | 3.41 | 3.55 | 3.66 | 3.73 | 3.76 | 3.81 | 4.05 | 4.40 | 4.32 | 4.29 | 4.23 | 4.15 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 4.320 |
| SC2 | 0 | 8 | 2.934 |
| SC3 | -18 | 7 | 2.414 |
| SC4 | -25 | 6 | 1.967 |
| SC5 | -34 | 6 | 1.899 |
| A | 1617 mm |
|---|---|
| B | 520 mm |
| C | 363 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1295 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø15,9 |
| Length | 1617 mm |
|---|---|
| Width | 520 mm |
| Height | 363 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.