EB-330BB6-B01 C
5.56 kW
Defrost: None
Product code: EB-330AC6-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,433 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 17.9 m² |
| Inner volume | 4.3 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 39 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EB-330AC6-B05 C | None |
|---|---|
| EB-330AC6-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.10 | 2.10 | 2.11 | 2.13 | 2.13 | 2.12 | 2.10 | 2.15 | 2.29 | 2.49 | 2.43 | 2.41 | 2.39 | 2.34 |
| 5 | 2.75 | 2.79 | 2.84 | 2.88 | 2.90 | 2.89 | 2.87 | 2.92 | 3.10 | 3.36 | 3.28 | 3.25 | 3.21 | 3.16 |
| 6 | 3.38 | 3.48 | 3.57 | 3.65 | 3.70 | 3.71 | 3.70 | 3.75 | 3.98 | 4.31 | 4.19 | 4.14 | 4.08 | 3.97 |
| 7 | 3.94 | 4.09 | 4.24 | 4.37 | 4.46 | 4.51 | 4.54 | 4.60 | 4.89 | 5.31 | 5.16 | 5.10 | 5.01 | 4.87 |
| 8 | 4.49 | 4.69 | 4.86 | 5.04 | 5.17 | 5.25 | 5.28 | 5.35 | 5.69 | 6.18 | 6.04 | 5.98 | 5.89 | 5.73 |
| 9 | 4.97 | 5.24 | 5.50 | 5.73 | 5.88 | 5.97 | 6.03 | 6.12 | 6.50 | 7.06 | 6.90 | 6.83 | 6.72 | 6.53 |
| 10 | 5.42 | 5.76 | 6.09 | 6.37 | 6.58 | 6.71 | 6.78 | 6.88 | 7.31 | 7.94 | 7.77 | 7.68 | 7.55 | 7.33 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.773 |
| SC2 | 0 | 8 | 5.354 |
| SC3 | -18 | 7 | 4.411 |
| SC4 | -25 | 6 | 3.570 |
| SC5 | -34 | 6 | 3.406 |
| A | 1617 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1295 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1617 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.