EB-240AC7-B01 C
9.07 kW
Defrost: None
Product code: EB-430AC4-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,956 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 33.0 m² |
| Inner volume | 5.9 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 53 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 70.5 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EB-430AC4-B01 C | None |
|---|---|
| EB-430AC4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.47 | 3.52 | 3.57 | 3.62 | 3.64 | 3.63 | 3.61 | 3.69 | 3.94 | 4.27 | 4.19 | 4.17 | 4.13 | 4.06 |
| 5 | 4.48 | 4.62 | 4.74 | 4.86 | 4.92 | 4.93 | 4.92 | 5.00 | 5.31 | 5.76 | 5.62 | 5.57 | 5.51 | 5.41 |
| 6 | 5.38 | 5.60 | 5.81 | 6.00 | 6.12 | 6.20 | 6.23 | 6.34 | 6.74 | 7.33 | 7.18 | 7.11 | 7.00 | 6.84 |
| 7 | 6.24 | 6.55 | 6.84 | 7.07 | 7.26 | 7.37 | 7.42 | 7.54 | 8.01 | 8.71 | 8.53 | 8.45 | 8.34 | 8.15 |
| 8 | 7.00 | 7.42 | 7.81 | 8.16 | 8.40 | 8.56 | 8.63 | 8.76 | 9.31 | 10.12 | 9.90 | 9.81 | 9.66 | 9.42 |
| 9 | 7.69 | 8.24 | 8.75 | 9.20 | 9.52 | 9.73 | 9.81 | 9.97 | 10.60 | 11.52 | 11.28 | 11.18 | 11.01 | 10.72 |
| 10 | 8.33 | 9.01 | 9.65 | 10.21 | 10.55 | 10.84 | 11.01 | 11.20 | 11.91 | 12.95 | 12.70 | 12.58 | 12.38 | 12.04 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.701 |
| SC2 | 0 | 8 | 8.757 |
| SC3 | -18 | 7 | 7.155 |
| SC4 | -25 | 6 | 5.806 |
| SC5 | -34 | 6 | 5.432 |
| A | 2037 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1715 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2037 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.