EB-430BC4-B05 C
9.18 kW
Defrost: None
Product code: EB-430AE7-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,070 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 31.3 m² |
| Inner volume | 8.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 55 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-430AE7-B05 C | None |
|---|---|
| EB-430AE7-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.64 | 3.63 | 3.64 | 3.66 | 3.66 | 3.64 | 3.60 | 3.71 | 3.95 | 4.30 | 4.21 | 4.19 | 4.16 | 4.12 |
| 5 | 4.73 | 4.76 | 4.81 | 4.86 | 4.88 | 4.86 | 4.81 | 4.90 | 5.21 | 5.65 | 5.49 | 5.43 | 5.35 | 5.24 |
| 6 | 5.79 | 5.89 | 5.99 | 6.09 | 6.14 | 6.14 | 6.08 | 6.16 | 6.53 | 7.08 | 6.85 | 6.76 | 6.63 | 6.42 |
| 7 | 6.81 | 6.98 | 7.16 | 7.33 | 7.42 | 7.44 | 7.39 | 7.47 | 7.91 | 8.56 | 8.28 | 8.17 | 8.00 | 7.71 |
| 8 | 7.74 | 8.00 | 8.26 | 8.50 | 8.66 | 8.72 | 8.71 | 8.80 | 9.32 | 10.08 | 9.77 | 9.62 | 9.41 | 9.06 |
| 9 | 8.60 | 8.96 | 9.30 | 9.61 | 9.80 | 9.91 | 9.93 | 10.05 | 10.66 | 11.54 | 11.23 | 11.08 | 10.85 | 10.44 |
| 10 | 9.47 | 9.92 | 10.35 | 10.72 | 10.95 | 11.10 | 11.14 | 11.28 | 11.95 | 12.94 | 12.60 | 12.43 | 12.18 | 11.76 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.598 |
| SC2 | 0 | 8 | 8.797 |
| SC3 | -18 | 7 | 7.372 |
| SC4 | -25 | 6 | 5.991 |
| SC5 | -34 | 6 | 5.818 |
| A | 2037 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1715 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2037 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.