EB-330BE4-B01 C
8.98 kW
Defrost: None
Product code: EB-430BC6-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,554 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 28.4 m² |
| Inner volume | 6.9 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 60 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.4 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-430BC6-B01 C | None |
|---|---|
| EB-430BC6-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.38 | 3.32 | 3.29 | 3.29 | 3.27 | 3.25 | 3.22 | 3.27 | 3.47 | 3.76 | 3.68 | 3.65 | 3.61 | 3.55 |
| 5 | 4.52 | 4.48 | 4.47 | 4.48 | 4.47 | 4.44 | 4.40 | 4.44 | 4.71 | 5.10 | 4.97 | 4.93 | 4.87 | 4.78 |
| 6 | 5.67 | 5.68 | 5.71 | 5.76 | 5.77 | 5.74 | 5.70 | 5.73 | 6.07 | 6.57 | 6.38 | 6.31 | 6.22 | 6.07 |
| 7 | 6.80 | 6.87 | 6.97 | 7.07 | 7.11 | 7.11 | 7.07 | 7.11 | 7.53 | 8.14 | 7.90 | 7.81 | 7.67 | 7.46 |
| 8 | 7.82 | 7.98 | 8.15 | 8.33 | 8.45 | 8.51 | 8.50 | 8.54 | 9.05 | 9.79 | 9.51 | 9.39 | 9.23 | 8.95 |
| 9 | 8.76 | 9.00 | 9.24 | 9.48 | 9.65 | 9.74 | 9.79 | 9.88 | 10.49 | 11.38 | 11.13 | 11.02 | 10.83 | 10.51 |
| 10 | 9.72 | 10.03 | 10.35 | 10.62 | 10.84 | 10.97 | 11.04 | 11.15 | 11.84 | 12.84 | 12.56 | 12.43 | 12.24 | 11.92 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.558 |
| SC2 | 0 | 8 | 8.540 |
| SC3 | -18 | 7 | 7.091 |
| SC4 | -25 | 6 | 5.713 |
| SC5 | -34 | 6 | 5.680 |
| A | 2357 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2357 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.