EB-430BC7-B01 C
8.29 kW
Defrost: None
Product code: EB-430BC6-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,960 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 28.4 m² |
| Inner volume | 6.9 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 56 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-430BC6-B05 C | None |
|---|---|
| EB-430BC6-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.20 | 3.14 | 3.12 | 3.12 | 3.10 | 3.09 | 3.06 | 3.12 | 3.32 | 3.60 | 3.52 | 3.50 | 3.46 | 3.41 |
| 5 | 4.27 | 4.22 | 4.22 | 4.22 | 4.21 | 4.19 | 4.15 | 4.20 | 4.46 | 4.83 | 4.71 | 4.68 | 4.62 | 4.55 |
| 6 | 5.34 | 5.34 | 5.36 | 5.40 | 5.41 | 5.38 | 5.34 | 5.38 | 5.71 | 6.17 | 6.00 | 5.93 | 5.84 | 5.71 |
| 7 | 6.41 | 6.46 | 6.53 | 6.62 | 6.65 | 6.64 | 6.60 | 6.64 | 7.03 | 7.61 | 7.38 | 7.29 | 7.16 | 6.95 |
| 8 | 7.42 | 7.54 | 7.69 | 7.84 | 7.92 | 7.94 | 7.91 | 7.95 | 8.42 | 9.11 | 8.84 | 8.73 | 8.57 | 8.30 |
| 9 | 8.32 | 8.52 | 8.73 | 8.94 | 9.08 | 9.16 | 9.19 | 9.28 | 9.85 | 10.65 | 10.35 | 10.22 | 10.03 | 9.70 |
| 10 | 9.23 | 9.50 | 9.75 | 10.01 | 10.20 | 10.31 | 10.35 | 10.46 | 11.10 | 12.04 | 11.76 | 11.63 | 11.44 | 11.12 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.758 |
| SC2 | 0 | 8 | 7.949 |
| SC3 | -18 | 7 | 6.636 |
| SC4 | -25 | 6 | 5.364 |
| SC5 | -34 | 6 | 5.349 |
| A | 2357 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2357 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.