EB-430BC6-B05 C
8.32 kW
Defrost: None
Product code: EB-430BC7-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,636 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 24.8 m² |
| Inner volume | 6.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 60 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.4 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-430BC7-B01 C | None |
|---|---|
| EB-430BC7-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.12 | 3.06 | 3.02 | 3.01 | 2.99 | 2.96 | 2.94 | 2.97 | 3.15 | 3.41 | 3.33 | 3.31 | 3.27 | 3.21 |
| 5 | 4.20 | 4.15 | 4.13 | 4.13 | 4.11 | 4.08 | 4.04 | 4.06 | 4.31 | 4.66 | 4.54 | 4.50 | 4.44 | 4.36 |
| 6 | 5.30 | 5.28 | 5.30 | 5.32 | 5.32 | 5.29 | 5.25 | 5.27 | 5.58 | 6.03 | 5.85 | 5.79 | 5.70 | 5.57 |
| 7 | 6.37 | 6.42 | 6.48 | 6.56 | 6.59 | 6.58 | 6.54 | 6.56 | 6.95 | 7.51 | 7.28 | 7.19 | 7.07 | 6.87 |
| 8 | 7.40 | 7.52 | 7.66 | 7.80 | 7.88 | 7.90 | 7.88 | 7.91 | 8.38 | 9.06 | 8.79 | 8.69 | 8.53 | 8.28 |
| 9 | 8.31 | 8.50 | 8.70 | 8.92 | 9.06 | 9.15 | 9.19 | 9.28 | 9.85 | 10.65 | 10.36 | 10.24 | 10.05 | 9.74 |
| 10 | 9.23 | 9.49 | 9.73 | 10.00 | 10.19 | 10.31 | 10.38 | 10.48 | 11.12 | 12.07 | 11.80 | 11.69 | 11.51 | 11.21 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.803 |
| SC2 | 0 | 8 | 7.908 |
| SC3 | -18 | 7 | 6.575 |
| SC4 | -25 | 6 | 5.295 |
| SC5 | -34 | 6 | 5.298 |
| A | 2357 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2357 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.