Skip to Content

Unit cooler EB-445AC7-B01 C ED

Defrost: Electric

Unit cooler EB-445AC7-B01 C
Illustrative photo

Producer: Karyer · Line: EB (General)

Product code: EB-445AC7-B01 C ED

Cooling capacity i
21.23 kW
Air flow
20,790 m³/h
Fin spacing
7.0 mm
Air throw
19 m
Fans
4 × ⌀450 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EB — EB - economical unit cooler
  • B
    Number of fans: 4 — Number of fans (one digit).
  • C
    Fan diameter: 45 — Ø450 mm
  • D
    Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: C — 4 tube rows
  • F
    Fin spacing: 7 — Fin spacing about 7 mm
  • G
    Generation code: B — Generation B
  • H
    Fan data: 01 — Ø300: 230V/1Ph/50Hz, 4-pole; Ø350: 230V/1Ph/50Hz, 4-pole; Ø400: 230V/1Ph/50Hz, 4-pole; Ø450: 230V/1Ph/50Hz, 4-pole

Data

Evaporator
Air flow 20,790 m³/h
Air throw 19 m
External surface 48.4 m²
Inner volume 13.7 dm³
Fin spacing 7.0 mm
Fin materialAluminium
Net weight 128 kg
Fans
Quantity 4
Diameter 450 mm
Speed 1,310 rpm
Power 1,960 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 59.0 dB(A)
Sound power 81.0 dB(A)
Energy class E
Connections
Inlet Ø28
Outlet Ø35
Defrost
EB-445AC7-B01 C None
EB-445AC7-B01 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
20.444 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 7.71 7.75 7.78 7.81 7.76 7.67 7.55 7.63 8.05 8.66 8.38 8.28 8.14 7.92
5 10.25 10.53 10.78 10.98 11.05 11.02 10.91 11.04 11.71 12.64 12.26 12.13 11.95 11.68
6 12.41 12.90 13.36 13.77 14.03 14.19 14.24 14.47 15.39 16.71 16.36 16.22 15.98 15.59
7 14.47 15.19 15.85 16.44 16.80 17.05 17.17 17.43 18.53 20.14 19.70 19.54 19.29 18.88
8 16.29 17.29 18.21 19.03 19.59 19.96 20.16 20.44 21.74 23.64 23.10 22.90 22.60 22.10
9 17.97 19.27 20.48 21.56 22.33 22.74 23.05 23.44 24.94 27.14 26.58 26.35 26.00 25.40
10 19.49 21.12 22.65 23.85 24.85 25.55 26.00 26.47 28.18 30.69 30.13 29.87 29.47 28.76

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 30.125
SC2 0 8 20.444
SC3 -18 7 16.571
SC4 -25 6 13.356
SC5 -34 6 12.529

Dimensions

Dimension drawing of EB-445AC7-B01 C
Dimension drawing
Dimensions as drawn
A 2967 mm
B 650 mm
C 617 mm
F 445 mm
E1 668 mm
E2 650 mm
E 2635 mm
D IN 1 x Ø28
D OUT 1 x Ø35
Overall [mm]
Length 2967 mm
Width 650 mm
Height 617 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.