EB-445AE6-B01 C
29.07 kW
Defrost: Electric
Product code: EB-445AE4-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 16,734 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 115.1 m² |
| Inner volume | 20.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 146 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,960 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø35 |
| EB-445AE4-B01 C | None |
|---|---|
| EB-445AE4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.94 | 11.80 | 12.60 | 13.30 | 13.79 | 14.09 | 14.23 | 14.83 | 15.88 | 17.36 | 17.16 | 17.10 | 17.01 | 16.89 |
| 5 | ≈ 13.16 | 14.59 | 15.76 | 16.80 | 17.48 | 17.99 | 18.24 | 18.91 | 20.22 | 22.10 | 21.69 | 21.56 | 21.36 | 21.06 |
| 6 | ≈ 15.33 | 17.01 | 18.63 | 20.09 | 21.19 | 21.74 | 22.17 | 22.91 | 24.48 | 26.77 | 26.27 | 26.07 | 25.75 | 25.21 |
| 7 | ≈ 12.07 | ≈ 19.19 | 21.27 | 22.90 | 24.37 | 25.44 | 26.09 | 26.95 | 28.79 | 31.51 | 30.95 | 30.69 | 30.26 | 29.47 |
| 8 | not rated | ≈ 21.14 | 23.37 | 25.70 | 27.59 | 29.01 | 29.92 | 30.97 | 33.09 | 36.23 | 35.64 | 35.33 | 34.80 | 33.78 |
| 9 | ≈ 6.38 | ≈ 13.30 | ≈ 25.50 | 28.30 | 30.61 | 32.42 | 33.65 | 34.92 | 37.35 | 40.91 | 40.35 | 40.00 | 39.37 | 38.17 |
| 10 | 6.96 | ≈ 6.91 | ≈ 27.43 | 30.70 | 33.48 | 35.69 | 37.27 | 38.81 | 41.55 | 45.55 | 45.04 | 44.66 | 43.97 | 42.60 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 45.044 |
| SC2 | 0 | 8 | 30.967 |
| SC3 | -18 | 7 | 23.539 |
| SC4 | -25 | 6 | 18.627 |
| SC5 | -34 | 6 | 15.688 |
| A | 2967 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E2 | 650 mm |
| E | 2635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø35 |
| Length | 2967 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.