Skip to Content

EB (General)

Application
Cubic, Commercial
Air discharge
Single
Refrigerants
R134a, R22, R290, R32, R404A, R407A, R407B, R407C, R407F, R410A, R448A, R449A, R450a, R452a, R454A, R454C, R455A, R507A, R513a, R744
Capacity
0.64–32.06 kW
Fans
⌀200, ⌀250, ⌀300, ⌀350, ⌀400, ⌀450 mm
Max. working pressure
25 bar
EB (General)

Model nomenclature

How to read the model codes of this series, with an example.

  • A
    Model code (series) EB = EB - economical unit cooler
  • B
    Number of fans — Number of fans (one digit).
  • C
    Fan diameter — Fan diameter in cm (two digits; x10 = mm), e.g. 30=Ø300, 63=Ø630, 91=Ø910. 20 = Ø200 mm25 = Ø250 mm30 = Ø300 mm35 = Ø350 mm40 = Ø400 mm45 = Ø450 mm
  • D
    Dimensional data - coil size letter — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows — Second letter of the dimensional data = number of tube rows (coil depth): A=2, B=3, C=4, D=5, E=6, G=8, I=10, K=12 (alphabet position + 1). A = 2 tube rowsB = 3 tube rowsC = 4 tube rowsE = 6 tube rows
  • F
    Fin spacing — Nominal fin spacing in mm (1-2 digits). Karyer catalogue: 4=4.20, 6=6.00. The exact pitch is per model (e.g. 4 covers 3.8 to 4.6 mm). 4 = Fin spacing about 4 mm6 = Fin spacing about 6 mm7 = Fin spacing about 7 mm
  • G
    Generation code — Karyer design generation letter; Karyer publishes no further decoding. B = Generation BC = Generation C
  • H
    Fan data 01 = Ø300: 230V/1Ph/50Hz, 4-pole; Ø350: 230V/1Ph/50Hz, 4-pole; Ø400: 230V/1Ph/50Hz, 4-pole; Ø450: 230V/1Ph/50Hz, 4-pole05 = Ø200: 230V/1Ph/50Hz, 4-pole; Ø250: 230V/1Ph/50Hz, 4-pole; Ø300: 230V/1Ph/50Hz, 4-pole07 = Ø450: 400V/3Ph/50Hz, 4-pole
  • J
    Option suffix (variant) — Optional, on BRI variant codes only: " ED" = electric defrost variant; no suffix = standard variant. ED = Electric defrost
Model Cooling capacity [kW] i Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 % Fin spacing [mm] Fans Air throw [m] Air flow [m³/h] Defrost Variants
EB-230BB6-B05 C 3.29 kW 6.0 2 × ⌀300 7 2,637 None, Electric
Variants (2)
EB-325BA4-B05 C 3.42 kW 4.2 3 × ⌀250 6 2,725 None, Electric
Variants (2)
EB-425AA6-B05 C 3.45 kW 6.0 4 × ⌀250 6 3,604 None, Electric
Variants (2)
EB-420AC7-B05 C 3.45 kW 7.0 4 × ⌀200 4 1,726 None, Electric
Variants (2)
EB-420AB4-B05 C 3.46 kW 4.2 4 × ⌀200 4 1,734 None, Electric
Variants (2)
EB-230AC7-B05 C 3.50 kW 7.0 2 × ⌀300 7 2,336 None, Electric
Variants (2)
EB-230BB6-B01 C 3.52 kW 6.0 2 × ⌀300 8 2,930 None, Electric
Variants (2)
EB-425BA7-B05 C 3.54 kW 7.0 4 × ⌀250 6 3,687 None, Electric
Variants (2)
EB-230AB4-B05 C 3.57 kW 4.2 2 × ⌀300 7 2,363 None, Electric
Variants (2)
EB-225BC4-B05 C 3.60 kW 4.2 2 × ⌀250 5 1,653 None, Electric
Variants (2)
EB-325AB6-B05 C 3.63 kW 6.0 3 × ⌀250 6 2,557 None, Electric
Variants (2)
EB-135AC7-B01 C 3.63 kW 7.0 1 × ⌀350 12 2,706 None, Electric
Variants (2)
EB-325BB7-B05 C 3.73 kW 7.0 3 × ⌀250 6 2,690 None, Electric
Variants (2)
EB-230AB4-B01 C 3.74 kW 4.2 2 × ⌀300 7 2,664 None, Electric
Variants (2)
EB-230AC6-B05 C 3.74 kW 6.0 2 × ⌀300 6 2,289 None, Electric
Variants (2)
EB-230AC7-B01 C 3.79 kW 7.0 2 × ⌀300 7 2,636 None, Electric
Variants (2)
EB-230BC7-B05 C 3.86 kW 7.0 2 × ⌀300 7 2,524 None, Electric
Variants (2)
EB-135AC6-B01 C 3.93 kW 6.0 1 × ⌀350 11 2,674 None, Electric
Variants (2)
EB-325AB4-B05 C 3.93 kW 4.2 3 × ⌀250 6 2,479 None, Electric
Variants (2)
EB-230BB4-B05 C 3.94 kW 4.2 2 × ⌀300 7 2,549 None, Electric
Variants (2)
EB-425AA4-B05 C 3.97 kW 4.2 4 × ⌀250 6 3,527 None, Electric
Variants (2)
EB-425BA6-B05 C 3.97 kW 6.0 4 × ⌀250 6 3,672 None, Electric
Variants (2)
EB-230AC6-B01 C 4.01 kW 6.0 2 × ⌀300 7 2,591 None, Electric
Variants (2)
EB-420AC4-B05 C 4.02 kW 4.2 4 × ⌀200 4 1,669 None, Electric
Variants (2)
EB-325BB6-B05 C 4.04 kW 6.0 3 × ⌀250 6 2,666 None, Electric
Variants (2)
EB-230BC7-B01 C 4.14 kW 7.0 2 × ⌀300 8 2,818 None, Electric
Variants (2)
EB-325AC7-B05 C 4.15 kW 7.0 3 × ⌀250 6 2,461 None, Electric
Variants (2)
EB-230BC6-B05 C 4.16 kW 6.0 2 × ⌀300 7 2,480 None, Electric
Variants (2)
EB-230BB4-B01 C 4.17 kW 4.2 2 × ⌀300 8 2,840 None, Electric
Variants (2)
EB-330AB7-B05 C 4.19 kW 7.0 3 × ⌀300 7 3,788 None, Electric
Variants (2)
EB-230AC4-B05 C 4.22 kW 4.2 2 × ⌀300 6 2,156 None, Electric
Variants (2)
EB-420AE7-B05 C 4.25 kW 7.0 4 × ⌀200 3 1,628 None, Electric
Variants (2)
EB-135AC4-B01 C 4.29 kW 4.2 1 × ⌀350 11 2,588 None, Electric
Variants (2)
EB-425AB7-B05 C 4.42 kW 7.0 4 × ⌀250 6 3,446 None, Electric
Variants (2)
EB-425BA4-B05 C 4.44 kW 4.2 4 × ⌀250 6 3,632 None, Electric
Variants (2)
EB-230AC4-B01 C 4.46 kW 4.2 2 × ⌀300 7 2,478 None, Electric
Variants (2)
EB-325AC6-B05 C 4.47 kW 6.0 3 × ⌀250 6 2,429 None, Electric
Variants (2)
EB-230BC6-B01 C 4.47 kW 6.0 2 × ⌀300 8 2,777 None, Electric
Variants (2)
EB-230AE7-B05 C 4.48 kW 7.0 2 × ⌀300 6 2,035 None, Electric
Variants (2)
EB-325BC7-B05 C 4.49 kW 7.0 3 × ⌀250 6 2,585 None, Electric
Variants (2)
EB-140AC7-B01 C 4.51 kW 7.0 1 × ⌀400 12 3,503 None, Electric
Variants (2)
EB-330AB6-B05 C 4.55 kW 6.0 3 × ⌀300 7 3,722 None, Electric
Variants (2)
EB-330AB7-B01 C 4.56 kW 7.0 3 × ⌀300 8 4,228 None, Electric
Variants (2)
EB-325BB4-B05 C 4.66 kW 4.2 3 × ⌀250 6 2,600 None, Electric
Variants (2)
EB-230BC4-B05 C 4.69 kW 4.2 2 × ⌀300 7 2,364 None, Electric
Variants (2)
EB-230AE6-B05 C 4.69 kW 6.0 2 × ⌀300 6 1,981 None, Electric
Variants (2)
EB-230AE4-B05 C 4.71 kW 4.2 2 × ⌀300 5 1,858 None, Electric
Variants (2)
EB-135AE7-B01 C 4.73 kW 7.0 1 × ⌀350 11 2,506 None, Electric
Variants (2)
EB-330BB7-B05 C 4.78 kW 7.0 3 × ⌀300 8 4,001 None, Electric
Variants (2)
EB-425AB6-B05 C 4.79 kW 6.0 4 × ⌀250 6 3,408 None, Electric
Variants (2)

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.