EB (General)

Application
Cubic, Commercial
Air discharge
Single
Refrigerants
R134a, R22, R290, R32, R404A, R407A, R407B, R407C, R407F, R410A, R448A, R449A, R450a, R452a, R454A, R454C, R455A, R507A, R513a, R744
Capacity
0.64–32.06 kW
Fans
⌀200, ⌀250, ⌀300, ⌀350, ⌀400, ⌀450 mm
Max. working pressure
25 bar
EB (General)

Model nomenclature

How to read the model codes of this series, with an example.

  • A
    Model code (series) EB = EB - economical unit cooler
  • B
    Number of fans — Number of fans (one digit).
  • C
    Fan diameter — Fan diameter in cm (two digits; x10 = mm), e.g. 30=Ø300, 63=Ø630, 91=Ø910. 20 = Ø200 mm25 = Ø250 mm30 = Ø300 mm35 = Ø350 mm40 = Ø400 mm45 = Ø450 mm
  • D
    Dimensional data - coil size letter — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows — Second letter of the dimensional data = number of tube rows (coil depth): A=2, B=3, C=4, D=5, E=6, G=8, I=10, K=12 (alphabet position + 1). A = 2 tube rowsB = 3 tube rowsC = 4 tube rowsE = 6 tube rows
  • F
    Fin spacing — Nominal fin spacing in mm (1-2 digits). Karyer catalogue: 4=4.20, 6=6.00. The exact pitch is per model (e.g. 4 covers 3.8 to 4.6 mm). 4 = Fin spacing about 4 mm6 = Fin spacing about 6 mm7 = Fin spacing about 7 mm
  • G
    Generation code — Karyer design generation letter; Karyer publishes no further decoding. B = Generation BC = Generation C
  • H
    Fan data 01 = Ø300: 230V/1Ph/50Hz, 4-pole; Ø350: 230V/1Ph/50Hz, 4-pole; Ø400: 230V/1Ph/50Hz, 4-pole; Ø450: 230V/1Ph/50Hz, 4-pole05 = Ø200: 230V/1Ph/50Hz, 4-pole; Ø250: 230V/1Ph/50Hz, 4-pole; Ø300: 230V/1Ph/50Hz, 4-pole07 = Ø450: 400V/3Ph/50Hz, 4-pole
  • J
    Option suffix (variant) — Optional, on BRI variant codes only: " ED" = electric defrost variant; no suffix = standard variant. ED = Electric defrost
Model Cooling capacity [kW] i Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 % Fin spacing [mm] Fans Air throw [m] Air flow [m³/h] Defrost Variants
EB-445AC7-B07 C 21.55 kW 7.0 4 × ⌀450 20 21,611 None, Electric
Variants (2)
EB-345AE7-B01 C 21.68 kW 7.0 3 × ⌀450 17 13,791 None, Electric
Variants (2)
EB-435AE4-B01 C 21.83 kW 4.2 4 × ⌀350 12 9,355 None, Electric
Variants (2)
EB-345AE7-B07 C 22.15 kW 7.0 3 × ⌀450 17 14,470 None, Electric
Variants (2)
EB-440AC4-B01 C 22.33 kW 4.2 4 × ⌀400 14 13,366 None, Electric
Variants (2)
EB-445AC6-B01 C 22.50 kW 6.0 4 × ⌀450 19 20,426 None, Electric
Variants (2)
EB-345AE6-B01 C 22.65 kW 6.0 3 × ⌀450 16 13,465 None, Electric
Variants (2)
EB-440AE7-B01 C 23.43 kW 7.0 4 × ⌀400 14 12,920 None, Electric
Variants (2)
EB-440AE6-B01 C 24.48 kW 6.0 4 × ⌀400 14 12,715 None, Electric
Variants (2)
EB-345AE4-B01 C 25.19 kW 4.2 3 × ⌀450 15 12,556 None, Electric
Variants (2)
EB-445AC4-B01 C 26.00 kW 4.2 4 × ⌀450 18 19,397 None, Electric
Variants (2)
EB-440AE4-B01 C 26.89 kW 4.2 4 × ⌀400 13 12,076 None, Electric
Variants (2)
EB-445AE7-B01 C 27.93 kW 7.0 4 × ⌀450 17 18,378 None, Electric
Variants (2)
EB-445AE7-B07 C 28.26 kW 7.0 4 × ⌀450 18 19,284 None, Electric
Variants (2)
EB-445AE6-B01 C 29.07 kW 6.0 4 × ⌀450 17 17,944 None, Electric
Variants (2)
EB-445AE4-B01 C 32.06 kW 4.2 4 × ⌀450 16 16,734 None, Electric
Variants (2)

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.