Skip to Content

Unit cooler EC-A-120BE6-C25 C

Unit cooler EC-A-120BE6-C25 C
Illustrative photo

Producer: Karyer · Line: EC-A (Celling Type)

Product code: EC-A-120BE6-C25 C

Cooling capacity i
0.46 kW
Air flow
220 m³/h
Fin spacing
5.5 mm
Air throw
3 m
Fans
1 × ⌀200 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EC-A — EC-A - commercial ceiling-type evaporator, aluminium casing
  • B
    Number of fans: 1 — Number of fans (one digit).
  • C
    Fan diameter: 20 — Ø200 mm
  • D
    Dimensional data - coil size letter: B — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: E — 6 tube rows
  • F
    Fin spacing: 6 — Fin spacing about 6 mm
  • G
    Generation code: C — Generation C
  • H
    Fan data: 25 — Ø200: 230V/1Ph/50Hz, 4-pole

Data

Evaporator
Air flow 220 m³/h
Air throw 3 m
External surface 1.8 m²
Inner volume 0.3 dm³
Fin spacing 5.5 mm
Fin materialAluminium
Net weight 5 kg
Fans
Quantity 1
Diameter 200 mm
Speed 1,300 rpm
Power 65 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 34.0 dB(A)
Sound power 55.0 dB(A)
Energy class E
Connections
Inlet Ø1/4"
Outlet Ø1/4"
Defrost
EC-A-120BE6-C25 C None
EC-A-120BE6-C25 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
0.442 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 0.17 0.18 0.18 0.19 0.19 0.19 0.19 0.19 0.21 0.22 0.22 0.22 0.21 0.21
5 0.22 0.23 0.24 0.25 0.25 0.25 0.25 0.25 0.27 0.29 0.28 0.28 0.28 0.27
6 0.26 0.27 0.29 0.30 0.31 0.32 0.32 0.32 0.34 0.37 0.36 0.35 0.34 0.33
7 0.29 0.32 0.34 0.35 0.37 0.37 0.38 0.38 0.41 0.44 0.43 0.42 0.41 0.40
8 ≈ 0.32 0.35 0.38 0.40 0.42 0.43 0.44 0.44 0.47 0.51 0.50 0.49 0.48 0.46
9 ≈ 0.35 0.39 0.42 0.45 0.47 0.49 0.49 0.50 0.53 0.58 0.56 0.56 0.55 0.53
10 0.38 0.42 0.46 0.50 0.52 0.54 0.55 0.56 0.60 0.65 0.63 0.62 0.61 0.59

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 0.631
SC2 0 8 0.442
SC3 -18 7 0.360
SC4 -25 6 0.289
SC5 -34 6 0.260

Dimensions

Dimension drawing of EC-A-120BE6-C25 C
Dimension drawing
Dimensions as drawn
A 395 mm
B 125 mm
C 415 mm
E 180 mm
D 270 mm
D IN 1 x Ø1/4"
D OUT 1 x Ø1/4"
Overall [mm]
Length 395 mm
Width 415 mm
Height 125 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.