ED-A-A-225BC6-B24 C
1.62 kW
Defrost: None
Product code: ED-A-A-225CD6-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 937 m³/h |
|---|---|
| Air throw | 3 m |
| External surface | 6.3 m² |
| Inner volume | 2.2 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 12 kg |
| Quantity | 2 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 130 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 37.0 dB(A) |
|---|---|
| Sound power | 57.7 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø12,7 |
| ED-A-A-225CD6-B24 C | None |
|---|---|
| ED-A-A-225CD6-B24 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.63 | 0.65 | 0.66 | 0.67 | 0.68 | 0.68 | 0.67 | 0.69 | 0.74 | 0.80 | 0.78 | 0.78 | 0.77 | 0.76 |
| 5 | 0.81 | 0.84 | 0.86 | 0.89 | 0.90 | 0.91 | 0.90 | 0.92 | 0.98 | 1.06 | 1.03 | 1.02 | 1.01 | 0.98 |
| 6 | 0.97 | 1.02 | 1.06 | 1.10 | 1.13 | 1.14 | 1.14 | 1.16 | 1.23 | 1.34 | 1.30 | 1.28 | 1.26 | 1.22 |
| 7 | 1.12 | 1.19 | 1.26 | 1.31 | 1.35 | 1.38 | 1.38 | 1.41 | 1.49 | 1.62 | 1.58 | 1.56 | 1.53 | 1.48 |
| 8 | 1.26 | 1.35 | 1.43 | 1.51 | 1.56 | 1.59 | 1.61 | 1.64 | 1.74 | 1.90 | 1.85 | 1.83 | 1.80 | 1.74 |
| 9 | 1.38 | 1.49 | 1.60 | 1.69 | 1.76 | 1.80 | 1.83 | 1.86 | 1.98 | 2.15 | 2.11 | 2.08 | 2.05 | 1.99 |
| 10 | 1.51 | 1.64 | 1.77 | 1.88 | 1.96 | 2.01 | 2.04 | 2.09 | 2.22 | 2.41 | 2.36 | 2.34 | 2.30 | 2.23 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 2.364 |
| SC2 | 0 | 8 | 1.639 |
| SC3 | -18 | 7 | 1.332 |
| SC4 | -25 | 6 | 1.064 |
| SC5 | -34 | 6 | 0.983 |
| A | 570 mm |
|---|---|
| B | 830 mm |
| C | 150 mm |
| E | 620 mm |
| D | 300 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø12,7 |
| Length | 570 mm |
|---|---|
| Width | 830 mm |
| Height | 150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.